Loading...
FocusPRO
®
TH5000 Series
7 69-1922EFS—01
ENGLISH
10
0
M29388
System test System status
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
Press s / t to turn system on/off.
Press NEXT to advance to next test.
Press DONE to terminate system test.
Test number
System status
Tobegin,press and hold the s and t
buttons until the display changes
Installer setup
Setup function Settings & options (factory default in bold)
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
CAUTION: Compressor protection is bypassed during testing. To prevent equipment
damage,avoidcyclingthecompressorquickly
!
10 Heating system 0 Heat and fan turn off.
1 Stage1heatturnson.FanturnsonifSetupFunction1issetto1,
5,9or10ORSetupFunction3issetto1**Seepage6
2 Stage 2 heat turns on
3 Stage3heatturnson-TH5320U only
20 Emergency heating
system
0 Heat and fan turn off
1 Heat and fan turn on
2 Stage 2 heat turns on (auxiliary heat) - TH5220D only
30 Cooling system 0 Compressor and fan turn off
1 Compressor and fan turn on
2 Stage 2 compressor turns on
40 Fan system 0 Fan turns off
1 Fan turns on
9 Stage 1 compressor
cycle rate (CPH)
3 Recommended for most compressors
[Othercyclerateoptions:1,2,4,5or6CPH]
10 Stage 2 compressor
cycle rate (CPH)
3 Recommended for most compressors
[Othercyclerateoptions:1,2,4,5or6CPH]
12 Manual/Auto
changeover
0 Manual changeover (Heat/Cool/Off)
1 Auto changeover (Heat/Cool/Auto/Off)
2 Auto changeover only (Auto)
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
5 Five-minute compressor off time
[Otheroptions:0,1,2,3or4-minuteofftime]
26 Auxiliary heat control 0 Comfort **See page 8
1 Economy
27 Heat temperature
range stops
90 Max. heat temperature setting is 90 °F (32 °C)
[Otheroptions:40°Fto89°F(4.5°Cto31.5°C)]
28 Cool temperature
range stops
50 Min. cool temperature setting is 50 °F (10 °C)
[Otheroptions:51°Fto99°F(10.5°Cto37°C)]