INSTALLATION INSTRUCTIONS
68-0281-16
L7224A,C; L7248A,C,L
Oil and Electric Boiler
Electronic Aquastat
®
Controllers
APPLICATION
The L7224A,C and L7248A,C,L 2012 Compliant
Electronic Aquastat
®
Controllers provide electronic
temperature sensing in a UL limit-rated control with a
single sensing probe. The L7224A,C and L7248A,C,L
control the circulator, oil or electric burner or contactor,
and boiler temperature. The L7224/L7248 is “Outdoor
Temperature Reset” ready which is enabled when
connected to the W8735Y1000 wireless or W8735S1000
wired Outdoor Reset Kit. Outdoor Reset with the L7224/
L7248 is intended for all applications except for tankless
coil systems for domestic hot water. Compliance to 2012
DOE regulation ensures efficiency is maximized without
interfering with domestic hot water demand.
The L7224A,C and L7248A,C,L replace the L8124A,
L8124C, L7124A,C, L7148A and L8148A Controllers.
The L7224A,C and L7248A,C,L series controls provide
status and diagnostic information through an LED display
combined with LED lights as well as EnviraCOM™
communications enabled thermostats and diagnostic
tools to enhance the diagnostic process.
L7224/L7248 Aquastat Controllers are intended for use
in residential-type applications.
IMPORTANT
Use of Outdoor Temperature Reset on a tank-
less coil application requiring a Low Limit setting
will result in reduced system effectiveness and
efficiency.
SPECIFICATIONS
Electrical Ratings:
Voltage: 120 Vac, 60 Hz.
Power: 7 VA maximum at 120 Vac plus external loads.
Thermostat current: 100 mA nominal at 24 Vac.
Burner Relay:
7.4 A at 120 Vac Full Load Amperage (FLA);
44.4 A inrush Locked Rotor Amperage (LRA);
Less Ignition Load: 360 VA.
Circulator Relay:
7.4 A at 120 Vac FLA; 44.4 A inrush LRA.
Zone Controller (ZC): 7.4 A at 120 Vac FLA;
44.4 A inrush LRA.
NOTE: All loads combined cannot exceed 2000 VA.
Environmental Ratings:
Temperature: -30 °F to +150 °F (-34 °C to +66 °C).
Humidity: 0 to 95% relative humidity, noncondensing.
Approvals:
Underwriters Laboratories Inc. Component Recognized.
Canadian Underwriters Laboratories Inc. Component
Recognized.
2012 DOE Compliance and Operation
Operation of this control may delay the burner operation while the residual heat is
circulated out of the boiler.
NOTE: This operation may be different than earlier electronic Aquastat
®
revisions which did not implement thermal purge.

Questions and Answers:

Honeywell L7248L Specifications

General IconGeneral
BrandHoneywell
ModelL7248L
CategoryController
LanguageEnglish

Summary

Application Overview

Product Specifications

Electrical Ratings

Details voltage, power consumption, and current ratings for various relays.

Environmental Conditions

Specifies the operating temperature and humidity limits for the device.

Regulatory Approvals

Lists the safety and compliance certifications obtained by the product.

Installation Guidelines

Critical Installation Precautions

Highlights critical warnings and advice for safe and effective installation.

Compatible Accessories

Installation Procedures

Step-by-Step Installation

Provides essential steps to follow before and during the installation of the product.

Mounting and Dimensions

Details the physical mounting methods and provides critical dimensional data.

New System Installation

New Installation Steps

Step-by-step guide for installing the Aquastat controller in a new system.

Installation Notes and Sensor Fit

Important advice for ensuring proper sensor fit and thermal response during installation.

Aquastat Controller Replacement

Flush-Mounted Replacement Guide

Instructions for replacing a flush-mounted Aquastat unit.

Well-Mounted Replacement Guide

Procedures for replacing a well-mounted Aquastat unit.

Sensor Replacement Process

Sensor Replacement Steps

Detailed guide on how to remove and install the sensor element safely.

Wiring Safety and Precautions

Critical safety warnings and electrical code compliance for wiring the controller.

Fuse and EnviraCOM Circuit

Aquastat Operation Basics

Adjustable Control Settings

High and Low Limit Adjustments

Covers adjustment of High Limit, Low Limit, and their differentials.

Outdoor Reset Configuration Parameters

Configuration of parameters for the optional Outdoor Reset Module.

Accessing Adjustment Mode

Describes the button sequence required to access and change settings.

Display Screen Interpretation

Display Readout Meanings

Controller Operational States

Normal Operating State

Behavior of the controller during normal heating and standby cycles.

Limit Control Operations

How the controller manages burner and circulator based on temperature limits.

Anti Short-Cycle Protection

Thermal Purge Functionality

Thermal Purge Configuration

Pump Cycling Maintenance

System Validation and Diagnostics

System Checkout Procedure

Steps to verify proper system operation after installation.

Troubleshooting Common Issues

Guidance for diagnosing and resolving system performance issues using error codes.

System Operating Sequences

Standard Sequence of Operations

System responses to various actions and error conditions in normal operation.

ZR Terminal Multi-Zone Sequences

Controller behavior with multiple zones connected via the ZR terminal.

Advanced Terminal Sequences

External Low Limit Terminal Sequences

Sequences when an external low limit device is connected to the ZR terminal.

Domestic Hot Water (DHW) Terminal Sequences

Controller responses when the ZR terminal is used for DHW calls.

Error Code Reference

Troubleshooting Diagnostic Guide

Troubleshooting Guide - Continued