PW7K1ICE Wiring and Setup
DIP Switch Configuration
PW7K1ICE Installation and Configuration Guide, Document 800-26497 21
2.4 DIP Switch Configuration
The four switches on S1 DIP switch configure the operating mode of the LP1501
processor. DIP switches are read on power up except where noted. read on power-
up except where noted
.
All other switch settings are unassigned and are reserved for future use.
2.5 Factory Default Communication Parameters
Table 2-3: DIP Switch Settings
1 2 3 4 Description
OFF OFF X OFF Normal operating mode.
ON X X X After initialization, enable default User Name (admin)
and Password (password). The switch is read on the
fly, no need to re-boot. See IT security section for
additional information.
OFF ON X OFF Use factory default communication
parameters.
ON ON X OFF Use OEM default communication
parameters. Contact system manufacture for details.
See Bulk Erase below.
ON ON OFF OFF
Bulk Erase prompt mode at power up. See Bulk Erase
below.
X X X ON
Makes the LP1501 report and function like an
PW6K1ICE ( EP1501). To be used in situations where
the host software has not been updated to support the
LP series product line
Table 2-4: Factory Default Communication Parameters
Parameter Default Value
Network static IP address 192.168.0.251
Communication address 0
Host port IP server, no encryption, port 3001
Interface 1 (NIC1)
Subnet Mask 255.255.0.0
Default Gateway 192.168.0.1
DNS Server 192.168.0.1