Honeywell M9484 - Internal Wiring and Adjustments; Internal Wiring Diagrams; Terminals and Adjustment Points

Honeywell M9484
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CLOSE
LIMIT
DIRECTION OF MOTOR TRAVEL AS VIEWED FROM POWER END.
&
CONNECT 24V POWER TO
Tl-T2
TERMINALS ONLY. DO NOT CONNECT
POWER SUPPLY TO CONTROLLER TERMINALS. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION AS REQUIRED.
n
3 TURN
LIMIT
POT FULL
CLOCKWISE~FOR
160’
STROKE, FULL
COUNTERCLOCKWISEr?FOR
90’
STROKE.
FIG.
5-lNTERNAL
WIRING OF
An9494
MODUTROL
MOTORS.
A
BLUE LEAD
I
A
YELLOW LEAD
REDLEAD
2
‘n
n
1
WIRING SHOULD BE NEC CLASS 1 UNLESS POWER SUPPLY
MEETS CLASS 2 REQUIREMENTS. TAPE UNUSED LEADS. MAKE
CERTAIN THE CURRENT DRAW OF THE EXTERNAL CIRCUIT IS
LESS THAN CONTACT RATING OF SWITCH.
1
A
n
2
ON TWO-SWITCH MOTORS SECOND SWITCH HAS BLACK
LEADS WITH BLUE, YELLOW. AND RED TRACERS.
M
254
I
FIG.
6-AUXILIARY
SWITCH INTERNAL WIRING.
MINIMUM
STROKE
ADJUSl
:zTloN
CAMS (YELLOW)
I
INNER AUXILIARY
INNER AUXILIARY
SWITCH CAM (BLUE)
OUTER AUXILIARY
SWITCH CAM (RED)
*
OUTER AUXILIARY
STROKE POT
NOTE: FEATURES AVAILABLE ON SOME MODELS ONLY.
M
ml/\
FIG. 7-TERMINALS AND ADJUSTMENTS.
63-2195-l