PRODUCT DATA
Global Field Devices
VRN Pressure Independent Control 
Valves and Actuators
APPLICATION
The VRN2 two-way pressure independent control valves 
maintain constant flow of hot or chilled water with glycol 
solutions up to 50% in closed-loop heating, ventilating, 
and air conditioning (HVAC Division 23) systems 
regardless of head pressure fluctuations above the 
minimum specified pressure drop. These valve assemblies 
can be used with Honeywell non-spring return or spring 
return direct coupled actuators (DCA).
The built-in differential pressure regulator makes fluid 
flow through the valve independent of changes in supply 
pressure, eliminating “hunting” by the control system, 
even at low coil flow. The pressure regulator virtually 
eliminates cavitation in the valve, and decouples the 
control valve from the effects of piping components such 
as reducers and elbows.
Pressure independent control valves are sized to match 
design coil flow regardless of coil size. VRN2 valves 
eliminate the need to balance the system for proper flow, 
and allow chillers to be operated at design temperature 
differential for maximum efficiency at every load 
condition. When used in a system with variable speed 
pump drives, 3-way valves and coil bypass lines are not 
required. In new construction, VRN2 valves perform better 
than reverse return piping designs without the extra 
materials these systems need.
Pressure-independent control requires less flow, enabling 
use of smaller piping, pumps, and chillers.
FEATURES
• Sizes from 1/2 to 3 in. with internal (female) NPT 
connections.
• Controls hot or chilled water with up to 50% glycol.
• Regulated flow rates available from 1 to 95 gpm.
• Differential pressure regulator for constant pressure 
drop across valve seat.
• Positive pressure, rolling diaphragm regulator design 
for flow control accuracy of ±5%.
• Equal percentage flow characteristic using patented 
flow control ball insert.
• Multiple maximum flow rates available per valve size.
• Patented ball seals for low operating torque.
• Nickel-chrome plated brass or stainless steel trim.
• Choice of factory-installed actuation using 
Honeywell MVN or MN/MS series direct coupled 
actuators: Floating, Modulating (2-10 V), Non-Spring 
Return and Spring Return.
• Spring return actuators field-configurable for 
normally open or normally closed fail-safe position.
• Removable, manual operating handle to control 
valve during installation or in an event of power 
failure.
• Upstream Test Port for venting or pressure gauge 
attachment.
• Three actuator orientations on the valve for cramped 
spaces.
• Integral snubber eliminates effect of system 
pressure fluctuations and entrapped air while 
improving flow performance.
Contents
Application ..................................................................................... 1
Features .......................................................................................... 1
Specifications ............................................................................... 2
Ordering Information  ................................................................ 2
Typical Specifications  ............................................................... 12
Installation .................................................................................... 13
Operation and Checkout .......................................................... 18