INSTRUCTION SHEET
S4560
AUTOMATIC IGNITION CONTROL
MU1R--9086 0009R9--NE
APPLICATION
The S4560 provides automatic ignition and control for burners
in accordance with EN 298.
SPECIFICATIONS
Model
S4560: 220 ... 240 V, 50 Hz.
Suffix A: For atmospheric burners. Non volatile lock out in
accordance with EN 298.
Suffix B: As suffix A except a built in flame indication relay for
modulating applications.
Suffix C: For fan assisted applications. Non volatile lock out in
accordance with EN 298.
Suffix D: As suffix C except a built in flame indication relay for
modulating applications.
Suffix E: As suffix A except lock--out after flame lost during
normal operation.
Suffix P: As suffix A except volatile lock out, reset by
interrupting heat demand.
Suffix Q: As suffix B except volatile lock out, reset by
interrupting heat demand.
Suffix R: As suf fix C except volatile lock out,reset by
interrupting heat demand.
Suffix T: As suffix D except volatile lock out, reset by
interrupting heat demand.
Dimensions
See fig. 9.
Ambient temperature
0 ... 60 _C
Relative humidity
90% max. at 40 _C (non condensing)
Supply voltage
Line voltage, 220 V (--15%) ... 240 V (+10%), 50 Hz (¦ 2Hz)
Power consumption
10 VA max.
Electrical rating
Valve(s) output: 1 A max cos > 0.6
Fan output (Suffix C, D, R and T): 1 A max cos > 0.6
Alarm output: 1 A max cos > 0.6
Flame indication relay: 1 A max cos > 0.6
External ignition transformer: 1 A max cos > 0.6
All outputs together: 3 A max.
Electrical connection
High tension spark: 2.8 x 0.5 mm spade terminal.
Flame rod and ground: 6.3 x 0.8 or 4.8 x 0.8 mm spade
terminal (depending on O.S. number).
Multiple connector: Molex 3001 series
Timing (depending on O.S. number)
Waiting time (T
w
)/Prepurge time (T
p
): 0 ... 24 s
Safety time (T
s
): 0 ... 250 s
Stabilization time (T
stab
): 0 ... 15 s
Flame sensing
Flame sensing is based on the rectification principle.
Minimum flame c u rrent: 0.7 A
Response time ”ON”: < 200 ms (at 2 A flame current)
Response time ”OFF”: < 1 s
Maximum cable length: 1 m
Not protected against electrical shock.
Ignition
Integral electronic spark generator
Spark voltage: 12 kV at 40 pF load
Repetition rate: 12 Hz
Maximum cable length: 1 m
Not protected against electrical shock.
Contents
English Page 1 ... 10...................................
Deutsch Seite 11 ... 13.................................
Nederlands Bladzijde 14 ... 16..........................
Subject to change without notice. Printed in the Netherlands.
Question and Answer IconNeed help?

Do you have a question about the Honeywell S4560 and is the answer not in the manual?

Honeywell S4560 Specifications

General IconGeneral
BrandHoneywell
ModelS4560
CategoryControl Unit
LanguageEnglish

Summary

APPLICATION

Overview

Introduces the S4560 for automatic ignition and control of gas burners per EN 298.

SPECIFICATIONS

Model Variants (Suffixes A-T)

Details S4560 models (suffixes A-T) and their specific features and lock-out types.

Physical Parameters

Covers dimensions, ambient temperature, and relative humidity limits.

Electrical Parameters

Details supply voltage, power consumption, output ratings, and connection types.

Timing and Sensing

Outlines timing settings, flame sensing principles, and ignition system details.

SYSTEM OPERATION

Atmospheric Appliances Operation

Describes the sequence for atmospheric burner ignition and control.

Fan Assisted Appliances Operation

Details the sequence for fan assisted burner ignition and control.

INSTALLATION AND CHECKOUT

Mounting and Reset

Guidance on physical mounting, optimal placement, and lock-out reset procedures.

WIRING AND TESTING

Wiring Precautions and Polarity

Covers wiring best practices, polarity checks, and terminal types.

Spark Gap, Flame Current, and Checkout

Details spark gap, flame current testing, and final verification steps.

General Considerations

Electrical compatibility, emissions, and EMC filtering advice.