INSTRUCTION SHEET
S4560
AUTOMATIC IGNITION CONTROL
MU1R--9086 0009R9--NE
APPLICATION
The S4560 provides automatic ignition and control for burners
in accordance with EN 298.
SPECIFICATIONS
Model
S4560: 220 ... 240 V, 50 Hz.
Suffix A: For atmospheric burners. Non volatile lock out in
accordance with EN 298.
Suffix B: As suffix A except a built in flame indication relay for
modulating applications.
Suffix C: For fan assisted applications. Non volatile lock out in
accordance with EN 298.
Suffix D: As suffix C except a built in flame indication relay for
modulating applications.
Suffix E: As suffix A except lock--out after flame lost during
normal operation.
Suffix P: As suffix A except volatile lock out, reset by
interrupting heat demand.
Suffix Q: As suffix B except volatile lock out, reset by
interrupting heat demand.
Suffix R: As suf fix C except volatile lock out,reset by
interrupting heat demand.
Suffix T: As suffix D except volatile lock out, reset by
interrupting heat demand.
Dimensions
See fig. 9.
Ambient temperature
0 ... 60 _C
Relative humidity
90% max. at 40 _C (non condensing)
Supply voltage
Line voltage, 220 V (--15%) ... 240 V (+10%), 50 Hz (¦ 2Hz)
Power consumption
10 VA max.
Electrical rating
Valve(s) output: 1 A max cos > 0.6
Fan output (Suffix C, D, R and T): 1 A max cos > 0.6
Alarm output: 1 A max cos > 0.6
Flame indication relay: 1 A max cos > 0.6
External ignition transformer: 1 A max cos > 0.6
All outputs together: 3 A max.
Electrical connection
High tension spark: 2.8 x 0.5 mm spade terminal.
Flame rod and ground: 6.3 x 0.8 or 4.8 x 0.8 mm spade
terminal (depending on O.S. number).
Multiple connector: Molex 3001 series
Timing (depending on O.S. number)
Waiting time (T
w
)/Prepurge time (T
p
): 0 ... 24 s
Safety time (T
s
): 0 ... 250 s
Stabilization time (T
stab
): 0 ... 15 s
Flame sensing
Flame sensing is based on the rectification principle.
Minimum flame c u rrent: 0.7 A
Response time ”ON”: < 200 ms (at 2 A flame current)
Response time ”OFF”: < 1 s
Maximum cable length: 1 m
Not protected against electrical shock.
Ignition
Integral electronic spark generator
Spark voltage: 12 kV at 40 pF load
Repetition rate: 12 Hz
Maximum cable length: 1 m
Not protected against electrical shock.
Contents
English Page 1 ... 10...................................
Deutsch Seite 11 ... 13.................................
Nederlands Bladzijde 14 ... 16..........................
Subject to change without notice. Printed in the Netherlands.
Question and Answer IconNeed help?

Do you have a question about the Honeywell S4560B1006 and is the answer not in the manual?

Honeywell S4560B1006 Specifications

General IconGeneral
BrandHoneywell
ModelS4560B1006
CategoryControl Unit
LanguageEnglish

Summary

Application

Specifications

System Operation

Operational Modes and Procedures

Details operation for atmospheric/fan-assisted burners, warnings, and lock-out reset procedures.

Installation and Checkout

Installation, Mounting, and Safety

Covers personnel, mounting, condensation warnings, and general installation safety requirements.

Wiring

Wiring, Testing, and Polarity

Guidelines for wiring, polarity, spark gap, flame current checks, and final checkout procedure.

General Considerations

External Fusing and Safety

Recommends external fusing, notes no serviceable parts, and mentions IP 40 rating for the appliance.

Thermostat Connection and RFI Suppression

Details connecting a high limit thermostat and suppressing RFI with shielded electrode cabling.

Related product manuals