62-0123—3
7
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Thermostat Information
1. Press the Heat/Cool Settings key to access the
thermostat information.
M4934
2. Press the increase ▲ key to display the production
date code. The first two large digits are the month
and the third digit is the last digit of the year.
(Example: 036 = March 1996)
M4931
3. Press the increase ▲ key again to display the
software identification code. (Example: 02 =
software ID code 2)
M4932A
4. Press the increase ▲ key again to display the
software revision number. (Example: 001 = revision
number 1)
M10229
Table 4. Installer Self-Test Options (Continued).
Key to
Press
Test
Number Description
Cooling Equipment System Test
Heat/Cool Settings 30 Change from heating to cooling equipment system test.
▲ 31 Stage-one cooling and system fan come on.
▲ 32 Stage-two cool comes on. Stage-one cool and system fan remain on.
▲ 33 Stage-three cool comes on (Q7300G only). Stage-one and stage-two cool with
system fan remain on.
▼ 32 Stage-three cool turns off.
▼ 31 Stage-two cool turns off.
▼ 30 Stage-one cool and system fan turn off.
Fan Equipment System Test
Heat/Cool Settings 40 Change from cooling to fan equipment system test.
▲ 41 Fan comes on.
▼ 40 Fan turns off.
Key Operation System Test
Heat/Cool Settings 60 2 Change from fan to key operation system test.
Unoccupied Temp 60 0 Unoccupied Temp test number is displayed.
Occupied Temp 60 1 Occupied Temp test number is displayed.
▲ 60 3 Increase test number is displayed.
▼ 60 5 Decrease test number is displayed.
Clear Start Time 60 7 Clear Start Time test number is displayed.
Day 60 8 Day test number is displayed.
Copy 60 9 Copy test number is displayed.
Unoccupied Start
TIme
60 10 Unoccupied Start Time test number is displayed.
System 60 11 System test number is displayed.
Fan 60 12 Fan test number is displayed.
Set Current
Day/Time
60 14 Set Current Day/Time test number is displayed.
Run Program 60 15 Run Program test number is displayed.
Temporary
Occupied
60 16 Temporary Occupied test number is displayed.
Occupied Start Time 60 17 Occupied Start Time test number is displayed.
Continuous
Unoccupied
60 19 Continuous Unoccupied test number is displayed.