A.3 Conditions of Use” for Ex Equipment”, Hazardous Location 
Equipment or “Schedule of Limitations”:  
a.  Consult the manufacturer for dimensional information on the flameproof 
joints for repair. 
b.  Painted surface of the RMA 800 series may store electrostatic charge and 
become a source of ignition in applications with a low relative humidity less 
than approximately30% relative humidity where the painted surface is 
relatively free of surface contamination such as dirt, dust or oil.  Cleaning of 
the painted surface should only be done with a damp cloth. 
c.  The ambient temperature range, maximum process temperature and 
applicable temperature class of the equipment is as follows: 
RMA801: T4 for -50˚C < Ta < 85˚C 
RMA803: T4 for -20˚C < Ta < 70˚C 
 
d.  The RMA800 series enclosure contains aluminum and is considered to 
present a potential risk of ignition by impact or friction. Care must be 
considered during installation and use to prevent impact or friction to avoid 
impact. 
e.  If a charge-generating mechanism is present, the exposed metallic part on 
the enclosure is capable of storing a level of electrostatic charge that could 
become incendive for IIC gases. Therefore, the user/installer shall 
implement precautions to prevent the buildup of electrostatic charge, e.g. 
earthing the metallic part. This is particularly important if the equipment is 
installed in a zone 0 location. 
f.  On installation, the RMA800 series shall be provided with supply transient 
protection external to the apparatus such that the voltage at the supply 
terminals of the RMA800 series does not exceed 140% of the voltage rating 
of the equipment.