Honeywell Smartronic70 T9275A1002 - Main Application: Heating Exchanger; Temperature Limit Control; Emergency Interlock

Honeywell Smartronic70 T9275A1002
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EC AP MKT
Page 11
Confidential and Proprietary
Main Application
AI
DI
AO
DO
HX
T
4. Heating Exchanger
Steam or hot water heating
exchanger temperature limit control
Heating is modulating output and
proportional to measured
temperature
Heating setpoint is in the mid of
proportional band
The temperature limit setpoint is
separate from the heating setpoint
If the measured temperature is over
than temperature limit, the system
alarm is on
Emergency Interlock
Under normal status, DI is closed. If
emergency happens, DI open. The
controller will reset all output, then
cut off the power.
The controller only can be restarted
by manual operation
Opened
100%
0%
50%
Closed
Heating mode
Temperature increase
Alarm
on
Heating setpoint
Alarming setpoint