EC AP MKT
Page 12
Confidential and Proprietary
Configuration & Operation
Item
Operation Display
Power On/Off Connect the main power. Display screen shows “DIGIT IN” and “OFF”.
Press the ‘SELECT’ key and hold more than 3 seconds, the controller turns on. It will read the setting value
in EPROM automatically. The controller is powered on.
After power on, LCD screen displays ambient temperature, output2 shows “DO OPEN”.
Press “select” key and hold more than 3 seconds, the product is powered off. And the display shows “OFF”.
Temperature
Adjustment
Press key S one time, the setting temperature will be 1
0
C up. Press and hold the key more than 2
seconds, the temperature increases continuously until reaches 60
0
C(internal sensor) or 110
0
C(remote
sensor). Press the button one more time to stop the temperature change.
Press the key T one time, setting temperature will be1
0
C down. Press it and hold more than 2 seconds,
the temperature decreases continuously until reaches 10
0
C(internal sensor) or -20
0
C(remote sensor).
Press the button one more time, the temperate change stops.
ZEB Value
Setting
Press “SELECT” 1 time to choose “Z BAND”.
Press key S 1 time “ST” switches between 1.5
0
C and 3.0
0
C.
Press key T 1 time “ST” switches between 3.0
0
C and 1.5
0
C.
Press “ENTER” one time to save the setting value.
If no input in 3 seconds, the controller will leave setting mode and return to normal operation mode
automatically.
Differential
Setting
Press “SELECT” to choose “DIFF”.
Press key S 1 time “ST” is 0.5
0
C up. The changing range is 0-3
0
C. The temperature will stop if the value
reaches 3
0
C
Press key T 1 time “ST” is 0.5
0
C down. The changing range is 3-0
0
C and the temperature will not change if
the value reaches 0
0
C.
Press “enter” to save setting value.