Honeywell Smartronic70 T9275A1002 - Main Application: Four Pipe AHU; Sequence Control

Honeywell Smartronic70 T9275A1002
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EC AP MKT
Page 10
Confidential and Proprietary
Main Application
Opened
Closed
100%
0%
50%
Output1: Heating Output2: Cooling mode
Temperature increase
Heating setpoint Cooling setpoint
Zero energy band
Setpoint centered in zero energy band
3. Four pipe AHU
Hot water heating coil + Water cooling
coil or sprayer sequence control
Setpoint is located in the mid of Zero
Energy Band
Cooling is 2 position output
Heating is modulating control and
proportional to measured temperature
Emergency Interlock
Under normal status, DI is closed. If
emergency happens, DI open. The
controller will reset all output, then cut
off the power.
The controller only can be restarted by
manual operation