Honeywell Smartronic70 T9275A1002 - Main Application: Two Pipe AHU (Heating;Cooling Sequence); Sequence Control Logic; Emergency Interlock Function

Honeywell Smartronic70 T9275A1002
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EC AP MKT
Page 9
Confidential and Proprietary
Main Application
Opened
Closed
100%
0%
50%
Output2: Heating
Output1: Cooling mode
Temperature increase
Heating setpoint Cooling setpoint
Zero energy band
Setpoint centered in zero energy band
2.Two pipe AHU
Water cooling coil +electrical heating
(or Hot water heating coil) Sequence
Control
Setpoint is located in the mid of Zero
Energy Band
Heating is 2 position output
Cooling is modulating control and
proportional to measured temperature
Emergency Interlock
Under normal status, DI is closed. If
emergency happens, DI open. The
controller will reset all output, then cut
off the power.
The controller only can be restarted by
manual operation