Page 14
Confidential and Proprietary
Configuration & Operation
Item
Operation Display
Reverse
Setting
Press “SELECT” to choose “REVERSE”.
Press key S “ST” value will switch between 0 and 1:
0Æ output1 in normal mode, 2—10Vdc or 4-20mA
1Æoutput1 in reversing mode, 10—2Vdc or 20-4mA
Press key T “ST” value will switch between 1 and 0.
Press, “ENTER” button to save setting value.
Display
Setting
Press “SELECT” to choose “DISPLAY”.
Press key S “ST” value will switch between 0 and 1.
0: Normal Mode, output1 is decimal value signal
1: Percentage Mode, output1 is percent value (2Vdc or 4mA--0% 10Vdc or 20mA--100%).
Press key T “ST” value will be 1 down.
Press, “ENTER” button to save setting value.
In percentage mode the screen will show “AO” and “%”.
Manual
Setting
Press “SELECT” to choose “MANUAL”.
Press key S “ST” value switches between 0 and 1: 0ÆMANUAL OFF 1ÆMANUAL ON
Press key T “ST” value switches between 1 and 0.
Press, “ENTER” button to save setting value.
If manual on, PV screen will show “AO” and “%”, ST screen shows measured value
If manual on, press key S 1 time, the displayed value will be 1% up. Hold the key 2 seconds up; the value
increases continuously until reaches 100%.
If manual on, press key T, the value will be 1% down. Hold the key 2 seconds up; the value decreases
continuously until reaches 0%.
After 90 minutes manual on operation, the controller will return to manual off mode automatically.
F1 Setting Press key “SELECT” to choose “F1”.
Press key S 1 time “ST” value will be 0.1 second up; the range is from 0.1 to 60 seconds. Hold the key 2
seconds up; the value increases 0.1 second until reaches 60.
Press the key T everything is reverse.
Press “ENTER” to save.
This value setting shows how long the output1 will update the output value.