EasyManua.ls Logo

Honeywell T775J - Page 19

Honeywell T775J
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
T775J ELECTRONIC REMOTE TEMPERATURE CONTROLLER
63-2248—4
19
Table 3. Checkout Table.
Checkout Table Checkout Table Example
Heat or
Cool Load 1 Load 2
Reset
Value
Load 1
Reset
Value
Load 2
Heat or
Cool
Load 1
Heat
Load 2
Heat
Reset
Value
Load 1
Reset
Value
Load 2
Sensor
A ____
Sensor
B ____
Sensed
Temp
Sensor A
80°
Sensor B
10°
Sensed
Temp
80° Off
76° On
80°
78° Off
74° On
120° Off
116° On
80°
118° Off
80°
Setpoint B ____________ Reset Direction __________ Setpoint B 30° Reset Direction Increase
Sensor B _____________ Reset Action ____________ Sensor B
10° Reset Action Below
Reset Ratio A _________ Reset Ratio B ___________ Reset Ratio A
1 Reset Ratio B 2
FORMULA 1: FORMULA 1 EXAMPLE:
Sensor B Sensor B = 10°F
-Setpoint B Setpoint B = 30°F
Temp Diff = _______________________ Temp Diff = -20°F
FORMULA 2: FORMULA 2 EXAMPLE:
Amount of Reset =
Reset Ratio B Amount of Reset = 2 x (-20) = -40
Reset Ratio A 1