T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
29 62-0257—11
Fig. 70. Program - Setpoint Offset (Loop 2 only).
 
Fig. 71. Reset Curve with Offset for Loop 2.
3.4. Loop 2 
For the second loop (if it is configured for Reset), the 
Offset parameter displays on the Program menu as 
shown in Fig. 70.
3.4.1. SETPOINT OFFSET (Loop 2 only)
This value is the number of degrees plus (+) or minus (-) 
that you want the temperature to be offset from the Loop 1 
setpoint. See Fig. 71. For example, If you want the Loop 2 
setpoint to be 10°F less than the Loop 1 setpoint, enter 
-10°F.
1. From the menu, use the  and  buttons to 
highlight OFFSET.
2. Press the  button to display the value.
3. Use the  and  buttons to increase/decrease the 
desired temperature.
OFFSET Default: 0°F
OFFSET Range: -150°F to 150°F (-101°C to 66°C)
4. Press the  button to accept the value and display 
the next option.
3.4.2. Loop 2 Programming
To complete the programming of Loop 2, perform the 
procedures in “3.3.5. THROTTLING RANGE” through 
“3.3.7. SETBACK OFFSET (if configured)” beginning on 
page 28.
3.4.3. Exit Loop Programming with 
Reset
When you finish programming the loop(s), press the 
HOME button to leave programming mode and return to 
the home screen.
If you have additional relays configured, continue with 
“3.5. Program Menus for the Additional Relays with 
Reset” on page 29.
If there are no additional relays, continue with “3.7. Exit 
Programming with Reset” on page 31.
Fig. 72. Program Menus for Relays.
3.5. Program Menus for the Additional 
Relays with Reset
Press the MENU button, select PROGRAM, then select 
an available relay to view the parameters. Fig. 72 shows 
the example for relay 9. If Relays are not set for Reset in 
Setup mode, simply enter the setpoint desired.
Up to two additional two relays can be available for 
independent on-off control. Examples of Loop and Relay 
configurations are:
• Number of relays = 8. Loop 1 uses relays 1-3, 
and Loop 2 uses relays 3-6. The remaining two 
relays (7 and 8) are available for use.
• Number of relays = 11. Loop 1 uses relays 1-5, 
and Loop 2 uses relays 6-10. The remaining 
relay (11) is available for use.
• Number of relays = 12. Loop 1 uses relays 1-4, 
and Loop 2 uses relays 5-8. Relays 9 and 10 
are available for use, but in this case, relays 11 
and 12 are not usable.
PROGRAM
  LOOP 2
MENU
PROGRAM
LOOP 2
OFFSET
-10
F
o 
ENTER
SETPOINT
OFFSET
FOR
LOOP 2
M24410
MENU
PROGRAM
LOOP 2
OFFSET
THROT RNG
HEAT/COOL
SETBACK
EXIT
SENSOR B
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
200
140
10
LOOP 2
SETPOINT
OFFSET
-10°F
190
20
30 40 50 60
70
°F80
150
160
170
210
220
180
°F
RESET B1
(OUTSD MIN)
RESET B2
(OUTSD MAX)
S
E
N
S
O
R
 
A
M24403
LOOP 1
SETPOINT
OFFSETDIFFRNTL
DIFFERENTIAL
SENSOR
HEAT/COOL
SETBACK
EXIT
PROGRAM
  RELAY 9
MENU
PROGRAM
RELAY 9
M24414