T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
15 62-0249—13
Fig. 32. Program - Differential or Throttling Range.
1.2.6. DIFFERENTIAL or THROTTLING 
RANGE
Differential displays for Relay outputs and Throttling 
Range is used for Modulating outputs.
1. From the menu, use the  and  buttons to high-
light DIFFERNTL or THROT RNG.
2. Press the  button to display the throttling range 
value.
3. Use the  and  buttons to increase/decrease the 
desired value. 
Default: 20° F (-07° C)
Range: 1° to 300° F (1° to 149° C)
4. Press the  button to accept the value and display 
the next option.
NOTES:
a. In heating mode, the Differential is below the 
setpoint. The relay de-energizes when the 
temperature rises to the setpoint. As the temperature 
drops to the setpoint minus the Differential, the relay 
energizes.
b. In cooling mode, the Differential is above the 
setpoint. The relay de-energizes when the 
temperature falls to the setpoint. As the temperature 
rises to the setpoint plus the Differential, the relay 
energizes.
c. The Throttling Range brackets the setpoint setting, 
e.g., if the setpoint is 72° F (22° C) and the 
throttling range is 10° F (-12° C), then the effective 
throttling temperature range is 67° to 77° F (17° to 
25° C). This applies to both modulating outputs 
and floating outputs.
Fig. 33. Program - Heat/Cool Selection.
1.2.7. HEAT/COOL
1. From the menu, use the  and  buttons to high-
light HEAT/COOL.
Default: HEAT
2. Press the  button to display the heat and cool 
selections.
3. Use the  and  buttons to select Heat or Cool.
4. Press the  button to accept the highlighted selec-
tion and display the Mod 1 menu.
5. Use the  and  buttons to highlight EXIT.
6. Press the  button to accept the value and display 
the next option. 
Fig. 34. Program - Setback.
1.2.8. SETBACK OFFSET (if configured)
The Setback temperature option displays only if 
scheduling is enabled (refer to Fig. 65 on page 26) or the 
DI Option is set to Setback (refer to Fig. 67 on page 27).
This value is the number of degrees plus (+) or minus (-) 
that you want the temperature to be offset from the 
setpoint. 
For example, If you want the temperature to be 10° F 
(-12° C) less than the setpoint during setback mode, enter 
-10° F (-12° C). In normal operations for heating, the 
offset will be negative. For cooling, the offset will be a 
positive value.
1. From the menu, use the  and  buttons to high-
light SETBACK.
2. Use the  and  buttons to increase/decrease the 
desired setpoint temperature.
Default: 0° F (-18° C)
Range: -150° to 150° F (-101° to 66° C)
3. Press the  button to accept the value and display 
the menu.
This completes the programming of the first Reset output. 
To program the subsequent outputs (e.g. MOD 2, Relay 2, Relay 3, etc.), continue with “1.2.9. Subsequent Outputs” on 
page 16.
ENTER
DIF-
ERENTIAL
FOR RELAY 1
PROGRAM
 RELAY 1
 DIFFRNTL
MENU
PROGRAM
RELAY 1
DIFFRNTL
20
F
o 
M24312
PROGRAM
 RELAY 1
 HEAT/COOL
MENU
PROGRAM
RELAY 1
HEAT/COOL
SELECT
HEAT/COOL
FOR 
RELAY 1
HEAT
COOL
M24313
PROGRAM
 RELAY 1
  SETBACK
MENU
PROGRAM
RELAY 1
SETBACK
-10
F
o 
ENTER
SETBACK
OFFSET
FOR RELAY 1
M24314