T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
23 62-0249—13
Fig. 55. Setup - Outputs - Modulating Output Menu.
3.3.3.1. Setting up the Modulating 
Outputs
1. From the Output menu, use the  and  buttons to 
highlight the desired modulating output (MOD 1 or 
MOD 2).
2. Press the  button to display the selected MOD 
menu.
NOTE: Modulating outputs are not available on 
controller models T775R2001 and 
T775R2035. If you are setting up one of these 
controllers, skip to “3.3.4. NBR OF RELAYS” 
on page 25.
Use the remaining procedures, beginning with “3.3.3.1.1. 
TYPE (of output signal)”, to set up each modulating 
output. If you have two modulating outputs, repeat these 
procedures for each modulating output.
Fig. 56. Setup - Outputs - Mod Out - Type.
3.3.3.1.1. TYPE (of output signal)
1. From the Mod menu, use the  and  buttons to 
highlight TYPE.
2. Press the  button to display the Type selections.
3. Use the and  buttons to highlight the desired 
output type.
Default: 4-20 mA
4. Press the  button to accept the selected type and 
return to the Mod menu.
Fig. 57. Setup - Outputs - Mod Out - Minimum 
Output Percentage.
3.3.3.1.2. MIN OUT %
The minimum output % prevents the output from dropping 
below the value entered. This value can be useful to 
maintain minimum damper position.
Using the time clock or digital input to disable the output 
forces the output to 0%.
1. From the Mod menu, use the  and  buttons to 
highlight MIN OUT %.
2. Press the  button to display the Min Out %.
3. Use the  and  buttons to increase/decrease the 
desired value from 0% to 100% in 1% increments.
Default: 0%
Range: 0 to 100%
4. Press the  button to accept the percentage and 
return to the Mod menu.
Fig. 58. Setup - Outputs - Mod Out - Integral.
3.3.3.1.3. INTEGRAL
1. From the Mod menu, use the  and  buttons to 
highlight INTEGRAL.
2. Press the  button to display the Integral seconds.
3. Use the  and  buttons to increase/decrease the 
value from 0 to 3,600 in 10 second increments. 
Default: 400 seconds
Range: 0 to 3,600 seconds
4. Press the  button to accept the seconds and 
return to the Mod menu.
SETUP
 
OUTPUTS
  MOD 1
SETUP
OUTPUTS
MOD 1
TYPE
MIN OUT %
INTEGRAL
DERIVATIV
SCHEDULE
RESET
EXIT
M24334
SETUP
 OUTPUTS
  MOD 1
 TYPE
SETUP
OUTPUTS
MOD 1
TYPE
SELECT
TYPE FOR
MOD 1
4 - 20 mA
0-10 V
2-10 V
SERIES 90
M24335
SETUP
  OUTPUTS
 MOD 1
      MIN OUT %
ENTER
MINIMUM
PERCENT FOR
MOD 1
SETUP
OUTPUTS
MOD 1
MIN OUT %
0
%
M24336
SETUP
  OUTPUTS
 MOD 1
   INTEGRAL
ENTER
INTEGRAL
TIME FOR
MOD 1
SETUP
OUTPUTS
MOD 1
INTEGRAL
400
SEC
M24337