1. SETUP T775U SERIES 2000 CONTROLLER 
19 62-0255–05
NOTES: (Integral Timing)
1. The Integral time is factory set for 400 seconds. This 
is a good middle range and should satisfy many 
applications. The integral time can be increased for 
applications where sensed response is slow, and can 
be decreased for applications where sensed 
response is fast (e.g. discharge air control).
2. As a starting point, an optimal integral time for 
discharge air typically ranges from 12 to 200 
seconds. An optimal integral time for room control 
typically ranges from 60 to 2,500 seconds. The 
purpose of integral action is to reduce or eliminate 
the offset from setpoint during steady state control 
that is often seen in proportional only control.
3. Keep in mind that control is most sensitive to 
throttling range. Adjust the throttling range first 
before any adjustment to integral time. Adjust 
throttling range to be as wide as possible to start 
since this will provide the most stable control. 
Remember that the integral will eliminate the steady 
state error so you do not need to have a small 
throttling range to have accurate control. (Integral 
action allows for controlling to a setpoint even with a 
wide throttling range).
Fig. 40. Setup - Outputs - Mod Out - Derivative.
1.3.1.4. DERIVATIVE
The Derivative default value is factory set to zero (no 
derivative control). It is strongly recommended that the 
derivative remain at zero (0) unless you have a very good 
reason to adjust it. Derivative control is not needed in the 
vast majority of HVAC applications.
1. From the Mod menu, use the S and T buttons to 
highlight DERIVATIV.
2. Press the X button to display the Derivative sec-
onds.
3. Use the S and T buttons to increase/decrease the 
value.
Default: 0 (zero)
Range: 0 to 3,600 seconds
4. Press the X button to accept the seconds and 
return to the Mod menu.
Fig. 41. Setup - Outputs - Mod Out - Schedule.
1.3.1.5. SCHEDULE
The Schedule option displays only if the USE SCHED 
parameter is set to Yes (see page 21).
1. From the Mod menu, use the S and T buttons to 
highlight SCHEDULE.
2. Use the S and T buttons to highlight YES or NO.
Default: YES
3. Press the X button to accept the selection and 
return to the Mod menu.
Each output can be set up to follow or ignore the built in 
scheduler. To disable the scheduler for all outputs, see 
“1.3.3.1. USE SCHED” on page 21.
SETUP
  OUTPUTS
 MOD 1
   DERIVATIV
ENTER
DERIVATIVE
TIME FOR
MOD 1
SETUP
OUTPUTS
MOD 1
DERIVATIV
0
SEC
M24603
SETUP
OUTPUTS
 MOD 1
 SCHEDULE
SETUP
OUTPUTS
MOD 1
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24604