TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS
69-1706 10
4. The Installer Setup Number is displayed in the
lower left. It is a four-digit code beginning with zero.
The factory setting or other choice selection is dis-
played in the lower right. See Fig. 23. This is a two-
digit code shown in the Option column of Table 4.
Fig. 23. Installer Setup Number and factory setting
selection locations.
Changing Installer Setup Selections
1. Advance to the next Installer Setup Number by
pressing the up and down arrow keys to the right of
the four-digit Installer Setup Number. See Fig. 23.
2. Change the factory Setting Options by pressing the
up and down arrow keys to the right of the two-digit
code selection. See Fig. 23.
Exiting Installer Setup
1. Press the Done key to exit the Installer Setup
screen.
IMPORTANT
The three Installer Setup Menus (Tables 4-6)
show all the available options. These options
customize themselves as you make selections
to the Installer Setup. Therefore, not all Installer
Setup Selections are shown or are available to
change.
INSTALLER
SETUP NUMBER
FACTORY
SETTING
ADVANCE TO NEXT
INSTALLER SETUP
PRESS TO EXIT
INSTALLER SETUP
CHANGE THE
FACTORY
SETTING
M19922
Table 4. Main Installer Setup Menu.
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Not used. 1 thru 0099 — — — — —
Date (Year
Upper)
0120 20 Set first two digits of
current calendar year
(20 for year 2005, etc)
21 21 —first two digits of
current calendar year
(21xx)
2000 -2178
available
Date (Year
Lower)
0130 04 Represents last two
digits of current
calendar year (2004).
00 -99 Select last two digits of
current calendar year.
2001-2178
available
Date (Month) 0140 6 Digit(s) represents
current calendar
month.
1-12 Select number that
represents current
calendar month.
—
Date
(Day)
0150 15 Digit(s) represents
current calendar date.
1-31 Select number that
represents current
calendar date.
—
Schedule
Options
0160 4 7-day programming 0 0 —nonprogrammable —