THERAPRO HR90
33-00084EFS—02 8
Parameters marked with an * are described in more detail
below.
Changing parameters
1. Keep the PROG button pressed for at least 10 sec-
onds until Parameter 1 flashes (left-hand digit).
The right-hand digit shows the current setting. The
parameter is displayed additionally in plain text. For
example, the display 1 1 stands for Parameter 1
(language) with Setting 1 (German).
2. Use the adjustment dial to select the desired
parameter (left-hand digit).
3. Press the OK button to edit the parameter.
The current setting of the parameter flashes (right
hand digit).
4. Use the adjustment dial to set the desired setting
(right-hand digit) and confirm with OK.
The parameter being edited flashes (left-hand digit).
5. For the further parameters repeat Steps 2 to 4.
6. Use the AUTO button to return to automatic mode.
Description of the parameters
Parameter 2 –Selecting the preset time
programs
• Week program 1 (factory setting, 2 setpoints):
Mo – Su (1 – 7) at home all day
This time program is described in Section 8.
• Week program 2 (6 setpoints):
Mo – Fr (1 – 5) lunch break at home
Sa – Su (6 – 7) like Week program 1
Table 1.
Par. Setting Meaning
1
1
2
3
4
5
6
Language setting
German
English
Danish
Swedish
Norwegian
Finnish
2
0
1
2
Preset time programs *
Week program 1 "At home all day"
Week program 2 "Lunch break at home"
Week program 3 "Part-time work"
3
0
1
Backlight *
Deactivated
Activated
4
0
1
Summer/winter time changeover
No automatic changeover
Automatic changeover
50
30
...
90
Duration of the window function *
Window function not active
Valve opens at the latest after 30 minutes
...
Valve opens at the latest after 90 minutes
6
0.2
...
2.0
Sensitivity of the window function during
dropping room temperature *
0.2 (sensitive)
...
2.0 (less sensitive)
Factory setting: 0.4
7
0.1
...
2.0
Sensitivity of the window function during
rising room temperature *
0.1 (sensitive)
...
2.0 (less sensitive)
Factory setting: 0.2
8
0
1
Setting the valve stroke *
Standard valve stroke
Full-stroke mode
9
0
1
Temperature representation in the display
*
Set/programmed temperature (setpoint
temperature)
Measured room temperature
10
16
17
...
30
Upper temperature limit
The room temperature cannot be set
higher than the specified upper
temperature limit (Max Limit).
Factory setting: 86 °F
11
5
6
...
15
Lower temperature limit
The room temperature cannot be set
lower than the specified lower
temperature limit (Min Limit).
Factory setting: 41 °F
12
0
1
2
Optimization function *
No optimization
Optimum start
Optimum start/stop
13
3
...
-3
Temperature offset *
To adjust the temperatures measured by
the radiator controller and in the room
Factory setting: 32 °F
14
0
1
2
Battery type
Alkaline
Lithium
NiMH (rechargeable batteries)
15
0
1
Display valve position *
No display of the valve position
Momentary display of the valve position
16
0
1
2
3
4
5
6
7
Valve exercise day *
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Off
17
0
1
2
Window open function *
Off (no window function)
Auto (corresponding to Parameters 5-7)
Cabled (with floating window contact)
18
0
1
Temperature unit
°Celsius
°Fahrenheit
19
0
1
2
3
Restore to factory setting
No reset
Reset only the basic settings
Reset only the time program
Reset all
Table 1. (Continued)
Par. Setting Meaning