Touchpoint Plus Safety Manual
4 Proof Test Procedure
4 Proof Test Procedure
4.1 Relay output proof test procedure
4.1.1 Force relay
The relays in Touchpoint Plus can be tested by using the menu of “Force Relay”. “Force Relay” is to verify relay operation regardless
of relay setting and gas sensor input. This is to verify if relay is energized or de-energized correctly. Please refer to the section 9.2.2
of 3011M5001 to conduct “Force Relay”. If any relays do not work correctly in force relay, please contact Honeywell Analytics for
further services.
4.1.2 Relay configuration
Channel relays will operate per user’s configuration. User is responsible for configuring each channel relay’s operation (energize or
de-energize) in the event of alarm 1, alarm 2, alarm 3, fault, inhibit and warning. Please refer to the section 6.4.16 of 3011M5001
to verify relay configuration. The user is responsible for relay configuration. It is highly recommend that user should check the relay
operation as configured. This can be done by relay simulator, described in user manual section 9.3.
4.1.3 Zero gas and relay
1) Apply zero gas to the sensor
2) The relay operation should be as intended per users relay configuration. If the relay operation is incorrect, refer to 6.15.2 (mV
input sensor) and 6.15.3 (mA input sensor) of 3011M5001 and complete a zero gas calibration procedure. Otherwise, please
contact Honeywell Analytics for further services.
4.1.4 Span gas and relay
1) Apply calibration gas to the sensor
2) The relay operation should be an intended per user’s realy configuration. If the relay operation is incorrect, refer to 6.15.2 (mV
input sensor) and 6.15.3 (mA input sensor) of 3011M5001 and complete a span gas calibration procedure. Otherwise, please
contact Honeywell Analytics for further services
4.2 mA output proof test procedure
4.2.1 Force mA
Each mA output channel of Touchpoint Plus can be tested by forcing the mA output. “Force 420 mA” is to verify mA output where
user can select the mA value and measure the mA output from Touch-point Plus by using the multimeter. Please refer to the section
9.2.3 of 3011M5001 to conduct “Force 420 mA.
Be sure that input channel and mA output channel configuration is correct before checking Force mA. The tolerance for mA output
shall be +/- 0.1 mA. For example, mA output is set at 4 mA in “Force 420 mA, then the actual measurement shall be ranged from
3.9 mA to 4.1 mA. Otherwise, please contact Honeywell Analytics for further services

Other manuals for Honeywell Touchpoint Plus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Touchpoint Plus and is the answer not in the manual?

Honeywell Touchpoint Plus Specifications

General IconGeneral
MountingPanel
CommunicationEthernet
Communication Ports1 x Ethernet, 2 x USB
Power Supply24 VDC
Enclosure RatingIP65 (front)

Related product manuals