V4043, V4044 VALVES; V8043, V8044 ZONE VALVES
9 95-6983—11
Fig. 25. Wiring a Honeywell V8043F to a Flair System
(2 options). (Wires are identified by letters for easy
correspondence to wires on Fig. 23.)
How to Replace a White-Rodgers 3-Wire
Valve with a Honeywell 2-Wire Valve
Fig. 26. Existing White-Rodgers System.
Fig. 27. Wiring a Honeywell V8043E to a White-
Rodgers System.
Fig. 28. Wiring a Honeywell V8043F to a White-
Rodgers System (one option).
Fig. 29. Wiring a Honeywell V8043F to a White-
Rodgers System (alternate option).
A
B
C
F
THERMOSTAT
END SWITCH
V8043F
TH-TR
TH
TR
L1
(HOT)
L2
1
E
M5966
A
B
C
F
THERMOSTAT
END SWITCH
V8043F
TH-TR
TH
TR
L1
(HOT)
L2
1
E
TO TERMINALS
T, T O N
BURNER RELAY
TO TERMINALS
T, T O N
BURNER RELAY
D
D
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
1
WATER VA LV E
THERMOSTAT
WHITE-RODGERS
1311 OR 1321
VALVE
TO AUXILIARY
CIRCUIT
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
M5711
1
2
3
4
5
6
4
56
1
1
L1
(HOT)
L2
THERMOSTAT
TO AUXILIARY
CIRCUIT
YELLOW
RED
RED
TO 6 ON
THERMOSTAT
TO
AUXILIARY
CIRCUIT
YELLOW
YELLOW
RED
RED
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT,
WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
TAPE UNUSED END AND TUCK INTO HOLE.
1
2
3
5
4
6
M5712
1
2
3
1
L1
(HOT)
L2
TO AUXILIARY
CIRCUITS
V8043F
END SWITCH
TH-TR
TH
TR
5
4
6
1
2
3
THERMOSTAT
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT,
WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
TAPE UNUSED END AND TUCK INTO HOLE.
1
2
3
TH
TR
TH-TR
END SWITCH
1
2
L1
(HOT)
L2
M5713
TO AUXILIARY
CIRCUITS
THERMOSTAT
END SWITCH
L1
(HOT)
L2
V8043F
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT,
WIRE AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
TAPE UNUSED END AND TUCK INTO HOLE.
1
2
3
1
2
3
4
5
6
L1
(HOT)
L2
1
TO
AUXILIARY
CIRCUIT
TO
AUXILIARY
CIRCUIT
2
END SWITCH
TH-TR
TH TR
M5714

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell V4043 and is the answer not in the manual?

Honeywell V4043 Specifications

General IconGeneral
Body MaterialBrass
Maximum Pressure125 psi
Frequency60 Hz
Operating Pressure125 psi
Maximum Operating Pressure125 psi
Actuator MaterialPlastic
End Connection TypeNPT
Voltage24 VAC
Size3/4 in., 1 in., 1-1/4 in.
Connection Size3/4", 1", 1-1/4"