62-0266 8
0670 Keypad
Lockout
0 0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked
Unlocked: All
functions
accessible.
Partial 1: Locks all
but Holiday,
Override, and Up/
Down.
Partial 2: Locks all
but Holiday and
Override.
Full: Entire
interface locked/
non-functional.
0680 Temperature
Control Heat
2 1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if
system has heat
stages.
Only integral gains
affected. Affects
control operation in
all control regimes
(not just recovery
or setpoint
change).
More Aggressive
stops signal prior to
reaching the
setpoint. (For use
with oversized
equipment.)
0685 Recovery
Heat Ramp
Rate
5 0-20° F/hour
(-18- -7° C)
Only shown if
system has heat
stages.
0 disables ramped
recovery (step
setpoint change at
period start time).
Table 1. Installer Setup (Continued).
Installer
Setup
Number
Installer
Setup
Name
Default
Setting All Settings Notes
62-0266.fm Page 8 Thursday, September 18, 2008 11:25 AM