InstallationSteps(continued)
ERV/HRVVentilationSystems69-2480EF—01 17
6
Connecting the power cord
ERV/HRV Power Cord
Insertthepowercordontopoftheunit.Pressfirmly
tomakesurethepowercordissecure.
IMPORTANT: Donotplugthepowercordintothe
wallreceptacleatthistime.
Electric Wall Outlet
Honeywellrecommendsthattheunithasadedicatedreceptacle
with120VAC.
Avoidconnectingtheunittothewallreceptaclewithan
extensioncord.
Honeywelldoesnotrecommendtheuseofanextensioncord.
Ensurethatthereceptacle’spolarizationiscorrect.
NOTE: IftheLEDlightontheERV/HRVcontrolpanelremainsgreen,themotorsdonotenergize,and
thecontrolsdonotoperate;thiscanindicatethatthepolarizationinthemainACoutletis
inverted.
IMPORTANT: Alwaysconsultaqualifiedtechniciantoensureproperinstallationofmainpower.
Installing outside hoods for the fresh air and the exhaust
7
Locatetheoutsidehoodsatleast18inches
(0.46m)abovegradeandatleast72inches
(1.83m)apart.
NOTE: Donotlocatethefreshairvent
hoodclosetoknownsourcesof
pollutantssuchasdryervents.
IMPORTANT: Alwaysconsultyour
localcodeforspacing
requirementsinyourarea.
72 (1,829)
18 (457)
M32372