95-7769—01 160
Nvi Bypass _value X X X X Units=%
Precision=1
Min=0.0
Max=100.0
Nvi Bypass _state X X X X Off
On
Default
Nvi Man Occ _occupancy X X X X Occupied
Unoccupied
Bypass
Standby
Default
Nvo A I Sensor _ai Val X X X Units=null
Precision=1
Min=-inf
Max=+inf
Nvo Remote Cmd _lev Percent X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Nvo Dig Cmd Free _value X X X Units=%
Precision=1
Min=0.0
Max=100.0
Nvo Dig Cmd Free _state X X X Off
On
Default
Nvo Appl Mode _hvac Mode X X X Default
Auto
Heat
Morning Warmup
Cool
Night Purge
Pre-cool
Off
Test
Emergency Heat
Fan Only
Free Cool
Ice
Maximum Heat
Economy
Dehumidify
Calibrate
Emergency Cool
Emergency Steam
Max Cool
HVAC Load
No Load
Nvo Econ Enable _value X X X Units=%
Precision=1
Min=0.0
Max=100.0
Nvo Econ Enable _state X X X Off
On
Default
Table 91. XL15C Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values