WEBVISION™
95-7769—01 162
Nvo F T Status _sensor Occupancy X X X Occupied
Unoccupied
Bypass
Standby
Default
Nvo F T Status _sys Mode X X X Auto
Heat
Morning Warmup
Cool
Night Purge
Pre-cool
Off
Test
Emergency Heat
Fan Only
Free Cool
Ice
Maximum Heat
Economy
Dehumidify
Calibrate
Emergency Cool
Emergency Steam
Default
Nvo F T Status _dlc Status X X X TRUE
Nvo F T Status _primary Cmd Percent X X X Units=%
Precision=0
Min=0.0
Max=255.0
Nvo F T Status _seq1 Cmd Percent X X X Units=%
Precision=0
Min=0.0
Max=255.0
Nvo F T Status _seq2 Cmd Percent X X X Units=%
Precision=0
Min=0.0
Max=255.0
Nvo F T Status _seq3 Cmd Percent X X X Units=%
Precision=0
Min=0.0
Max=255.0
Nvo F T Status _prim Activ Stages X X X Units=null
Precision=0
Min=0.0
Max=255.0
Nvo F T Status _seq1 Active Stages X X X Units=null
Precision=0
Min=0.0
Max=255.0
Nvo F T Status _seq2 Active Stages X X X Units=null
Precision=0
Min=0.0
Max=255.0
Nvo F T Status _seq3 Active Stages X X X Units=null
Precision=0
Min=0.0
Max=255.0
Nvo F T Status _prim Stage1 On X X X False or True
Nvo F T Status _prim Stage2 On X X X False or True
Table 91. XL15C Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values