PAGE 1 15 MAY 2006 MAN0808-01
HE-XE102 Specifications / Installation
1 SPECIFICATIONS
HE-XE102 Specifications
Digital DC Inputs
Inputs per Module 12 including 4 configurable
HSC inputs
Commons per Module 1
Input Voltage Range 12 VDC / 24 VDC
Absolute Max. Voltage 35 VDC Max.
Input Impedance
10 k
Input Current
Positive
Logic
Negative
Logic
Upper Threshold
0.8 mA -1.6 mA
Lower Threshold
0.3 mA -2.1 mA
Max Upper Threshold 8 VDC
Min Lower Threshold 3 VDC
OFF to ON Response 1 ms
ON to OFF Response 1 ms
HSC Max. Switching Rate 10 kHz
Digital Relay Outputs
Outputs per Module 6 relay
Commons per Module 6
Max. Output Current 5 A at 250 VAC, resistive
Max. Total Current 5 A continuous
Max. Output Voltage 275 VAC , 30 VDC
Max. Switched Power 150 W, 1250 VA
Contact Isolation to XLE ground 1000 VAC
Max. Voltage Drop at Rated Current 0.5 V
Expected Life No load: 5,000,000
Rated load: 100,000
Max. Switching Rate 300 CPM at no load
20 CPM at rated load
Type Mechanical Contact
Response Time One update per ladder
scan plus 10 ms
Analog Inputs, Medium Resolution
Number of Channels 4
Input Ranges
0 - 10 VDC
0 – 20 mA
4 – 20 mA
Safe input voltage range -0.5 V to +12V
Input Impedance
(Clamped @ -0.5 VDC to 12 VDC)
Current Mode:
100
Voltage Mode:
500 k
Nominal Resolution 10 Bits
%AI full scale 32,000 counts
Max. Over-Current 35 mA
Conversion Speed All channels converted
once per ladder scan
Max. Error at 25°C
TBD
Additional error for temperatures
other than 25°C
TBD
Filtering 160 Hz hash (noise) filter
1-128 scan digital running
average filter
General Specifications
Required Power
(Steady State)
130 mA @ 24 VDC
Required Power
(Inrush)
30 A for 1 ms @ 24 VDC
Primary Power
Range
10 – 30 VDC
Relative Humidity 5 to 95% Non-condensing
Operating
Temperature
0° to 50° Celsius
Terminal Type Screw Type, 5 mm Removable
Weight 12 oz. (340.19 g)
CE
UL
See Compliance Table at
http://www.heapg.com/Support/compliance.htm
2 Panel Cut-Out and Dimensions
Refer to XLE User Manual (MAN0805) for panel box information and a handy checklist of requirements.
Note: The tolerance to meet NEMA standards is ± 0.005” (0.1 mm).
3 Ports / Connectors / Cables
Note: The case of the XLE is black, but for clarity, it is shown in a lighter gray color.
X
LE OCS Model: HE-
X
E102
12 Digital DC Inputs
4 Analog Inputs (Medium Resolution)
6 Digital Relay Outputs
Want More Information?
To download the XLE User
Manual (MAN0805), refer to
Technical Support in this
document.
8
1
MJ1 Pins MJ2 Pins
Pin
Signal Direction Signal Direction
8
TXD OUT TXD OUT
7
RXD IN RXD IN
6
0 V Ground 0 V Ground
5
NC No Connect NC No Connect
4
CTS OUT TX- OUT
3
RTS IN TX+ OUT
2
RX- / TX- IN / OUT RX- IN
1
RX+ / TX+ IN / OUT RX+ IN
3.622 [92mm]
3.622 [92mm]
001XLE002
PRELIMINARY
Power Connector
Power Up:
Connect to Earth Ground.
A
pply 10 - 30 VDC.
Screen lights up.
CAN Connector
Use the CAN Connector when
using CsCAN network.
To Remove Back Cover:
Unscrew 4 screws located on
the back of the unit.
Lift lid.
CAUTION: Do not overtighten
screws when screwing the lid
back on.
I/O Jumpers: (Not Shown)
I/O Jumpers (JP) are located
internally. To access, remove
back cover of unit.
The I/O Jumpers, External
Jumpers and Connectors (J1
/ J2) are described in the
Wiring and Jumpers section
of this document.
Memory Slot:
Uses Removable Memory fo
r
data logging, screen captures,
program loading and recipes.
Horner Part No.: HE-MC1
Serial Communications:
MJ1: Use for Cscape
programming and Application-
Defined Communications.
MJ2: Use for Application-
Defined Communications

Other manuals for HORNER HE-XE102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HORNER HE-XE102 and is the answer not in the manual?

HORNER HE-XE102 Specifications

General IconGeneral
BrandHORNER
ModelHE-XE102
CategoryController
LanguageEnglish

Related product manuals