Field๎˜ƒInstallation๎˜ƒ
Field๎˜ƒInstallation๎˜ƒ
Safety๎˜ƒInformation๎˜ƒand๎˜ƒGuidelines๎˜ƒ
Only๎˜ƒqualified๎˜ƒservice๎˜ƒtechnicians๎˜ƒshould๎˜ƒ
attempt๎˜ƒto๎˜ƒinstall,๎˜ƒservice,๎˜ƒor๎˜ƒmaintain๎˜ƒthe๎˜ƒIce๎˜ƒ
Flaker.๎˜ƒ
Make๎˜ƒsure๎˜ƒall๎˜ƒpower๎˜ƒsources๎˜ƒare๎˜ƒdisconnected๎˜ƒ
before๎˜ƒany๎˜ƒservice๎˜ƒwork๎˜ƒis๎˜ƒdone๎˜ƒto๎˜ƒthe๎˜ƒIce๎˜ƒ
Flaker.๎˜ƒ
All๎˜ƒfield๎˜ƒwiring๎˜ƒmust๎˜ƒconform๎˜ƒto๎˜ƒthe๎˜ƒ
requirements๎˜ƒof๎˜ƒthe๎˜ƒequipment๎˜ƒand๎˜ƒall๎˜ƒ
applicable๎˜ƒlocal๎˜ƒcodes๎˜ƒand๎˜ƒnational๎˜ƒcodes.๎˜ƒ
Always
๎˜ƒrefer๎˜ƒto๎˜ƒthe๎˜ƒCondensing๎˜ƒUnit๎˜ƒ
manufacturerโ€™s๎˜ƒinstallation๎˜ƒmanual๎˜ƒfor๎˜ƒfurther๎˜ƒ
specification๎˜ƒand๎˜ƒguidance.๎˜ƒ
Inspection๎˜ƒ
Upon๎˜ƒreceipt,๎˜ƒcheck๎˜ƒall๎˜ƒitems๎˜ƒagainst๎˜ƒthe๎˜ƒbill๎˜ƒof๎˜ƒ
lading๎˜ƒto๎˜ƒmake๎˜ƒsure๎˜ƒall๎˜ƒcrates๎˜ƒand๎˜ƒcartons๎˜ƒare๎˜ƒ
accounted๎˜ƒfor.๎˜ƒ
Any๎˜ƒshortage๎˜ƒor๎˜ƒdamages๎˜ƒshould๎˜ƒbe๎˜ƒreported๎˜ƒto๎˜ƒ
the๎˜ƒdelivering๎˜ƒcarrier.๎˜ƒ๎˜ƒDamaged๎˜ƒmaterial๎˜ƒ
becomes๎˜ƒthe๎˜ƒdelivering๎˜ƒcarrierโ€™s๎˜ƒresponsibility๎˜ƒ
and๎˜ƒshould๎˜ƒnot๎˜ƒbe๎˜ƒreturned๎˜ƒto๎˜ƒthe๎˜ƒ
manufacturer๎˜ƒunless๎˜ƒprior๎˜ƒapproval๎˜ƒis๎˜ƒgiven.
๎˜ƒ
Take๎˜ƒcare๎˜ƒnot๎˜ƒto๎˜ƒdamage๎˜ƒequipment๎˜ƒwhen๎˜ƒ
uncrating.๎˜ƒ
Condensing๎˜ƒUnit๎˜ƒRigging๎˜ƒand๎˜ƒ
Mounting๎˜ƒ
Rigging๎˜ƒholes๎˜ƒare๎˜ƒprovided๎˜ƒon๎˜ƒall๎˜ƒunits.๎˜ƒ๎˜ƒCaution๎˜ƒ
should๎˜ƒbe๎˜ƒexercised๎˜ƒwhen๎˜ƒmoving๎˜ƒthese๎˜ƒunits.๎˜ƒ๎˜ƒ
To๎˜ƒprevent๎˜ƒdamage๎˜ƒto๎˜ƒthe๎˜ƒunit๎˜ƒhousing๎˜ƒduring๎˜ƒ
rigging,๎˜ƒcables๎˜ƒor๎˜ƒchains๎˜ƒused๎˜ƒmust๎˜ƒbe๎˜ƒheld๎˜ƒ
apart๎˜ƒby๎˜ƒspacer๎˜ƒbars.๎˜ƒ๎˜ƒThe๎˜ƒmounting๎˜ƒplatform๎˜ƒor๎˜ƒ
base๎˜ƒshould๎˜ƒbe๎˜ƒlevel๎˜ƒand๎˜ƒlocated๎˜ƒso๎˜ƒas๎˜ƒto๎˜ƒpermit๎˜ƒ
free๎˜ƒaccess
๎˜ƒof๎˜ƒsupply๎˜ƒair.๎˜ƒ
Ground๎˜ƒMounting๎˜ƒ
Concrete๎˜ƒslab๎˜ƒraised๎˜ƒsix๎˜ƒinches๎˜ƒabove๎˜ƒground๎˜ƒ
level๎˜ƒprovides๎˜ƒa๎˜ƒsuitable๎˜ƒbase.๎˜ƒ๎˜ƒRaising๎˜ƒthe๎˜ƒbase๎˜ƒ
above๎˜ƒground๎˜ƒlevel๎˜ƒprovides๎˜ƒsome๎˜ƒprotection๎˜ƒ
from๎˜ƒground๎˜ƒwater๎˜ƒand๎˜ƒwindโ€blown๎˜ƒmatter.๎˜ƒ๎˜ƒ
Before๎˜ƒtightening๎˜ƒmountin g๎˜ƒbolts,๎˜ƒrecheck๎˜ƒlevel๎˜ƒ
of๎˜ƒunit.๎˜ƒ๎˜ƒThe๎˜ƒunit๎˜ƒshould๎˜ƒin๎˜ƒall๎˜ƒcases๎˜ƒbe๎˜ƒlocated๎˜ƒ
with๎˜ƒ
a๎˜ƒclear๎˜ƒspace๎˜ƒin๎˜ƒall๎˜ƒdirections๎˜ƒthat๎˜ƒis๎˜ƒat๎˜ƒa๎˜ƒ
minimum,๎˜ƒequal๎˜ƒto๎˜ƒthe๎˜ƒheight๎˜ƒof๎˜ƒthe๎˜ƒunit๎˜ƒabove๎˜ƒ
the๎˜ƒmounting๎˜ƒsurface.๎˜ƒ๎˜ƒA๎˜ƒcondensing๎˜ƒunit๎˜ƒ
mounted๎˜ƒin๎˜ƒa๎˜ƒcorner๎˜ƒformed๎˜ƒby๎˜ƒtwo๎˜ƒwalls,๎˜ƒmay๎˜ƒ
result๎˜ƒin๎˜ƒdischarge๎˜ƒair๎˜ƒrecirculation๎˜ƒwith๎˜ƒ
resulting๎˜ƒloss๎˜ƒof๎˜ƒcapacity.๎˜ƒ
Roof๎˜ƒMounting๎˜ƒ
Due๎˜ƒto๎˜ƒthe๎˜ƒweight๎˜ƒof
๎˜ƒthe๎˜ƒunits,๎˜ƒa๎˜ƒstructural๎˜ƒ
analysis๎˜ƒby๎˜ƒa๎˜ƒqualified๎˜ƒengineer๎˜ƒmay๎˜ƒbe๎˜ƒrequired๎˜ƒ
before๎˜ƒmounting.๎˜ƒ๎˜ƒRoof๎˜ƒmounted๎˜ƒunits๎˜ƒshould๎˜ƒ
be๎˜ƒinstalled๎˜ƒlevel๎˜ƒon๎˜ƒsteel๎˜ƒchannels๎˜ƒor๎˜ƒan๎˜ƒIโ€beam๎˜ƒ
frame๎˜ƒcapable๎˜ƒof๎˜ƒsupporting๎˜ƒthe๎˜ƒweight๎˜ƒof๎˜ƒthe๎˜ƒ
unit.๎˜ƒ๎˜ƒ
Access๎˜ƒ
Provide๎˜ƒadequate๎˜ƒspace๎˜ƒat๎˜ƒthe๎˜ƒcompressor๎˜ƒend๎˜ƒ
of๎˜ƒthe๎˜ƒunit๎˜ƒfor๎˜ƒservicing.๎˜ƒ๎˜ƒ
Provide๎˜ƒadequate๎˜ƒ
space๎˜ƒon๎˜ƒthe๎˜ƒconnection๎˜ƒside๎˜ƒto๎˜ƒpermit๎˜ƒservice๎˜ƒ
of๎˜ƒcomponents.๎˜ƒ
๎˜ƒ
๎˜ƒ