Fixed in Fabric OS 6.2.0.
Workaround prior to upgrade:
Execute portdisable/porten-
able of F_Ports or switchdis-
able/switchenable or reboot the
switch.
Under some conditions N_Port Failover may not work when swapping
trunked and non-trunked N_Ports on an Access Gateway.
Fixed in Fabric OS 6.2.0.
Workaround prior to upgrade:
Use auto_elp mode.
Auto_ELP setting for EX_Port is not restored by configdownload.
Fixed in Fabric OS 6.2.0.
When running stressful IRNDUP to CUP tests, user may observe Inter-
mittent Channel Timeouts.
Fixed in Fabric OS 6.2.0.
Workaround prior to upgrade:
Increase cooling or relocate switch to
cooler location. Be sure switch is in-
stalled with proper spacing above
and below it.
Warnings of excessively high temperature seen on some HP Storage-
Works 8/40 SAN switches.
Fixed in Fabric OS 6.2.0.
Workaround prior to upgrade:
Rerun diagnotics by rebooting the
switch or powering on the slot with B-
series Multiprotocol Router blade.
POST (portloopback test) intermittently fails on 400 MP Router and
B-series MP Router blade.
Fixed in Fabric OS 6.2.0.
Zone Transaction appears to succeed in SMIA when the transaction
was aborted by web GUI.
Fixed in Fabric OS 6.2.0.
Port address from switchshow does not include offset used for Interop
mode 2.
Fixed in Fabric OS 6.2.0.
Workaround prior to upgrade:
Use portstatsshow to determine
whether there are CRC errors on a
link.
CRC errors did not match between portstatsshow and port-
errshow.
Fixed in Fabric OS 6.2.0.
Under rare conditions, an HP StorageWorks DC SAN Backbone Dir-
ector panics during SAK IRNDUP when the software watchdog detects
an unexpected termination of the FICON CUP daemon (ficud).
Fixed in Fabric OS 6.2.0.
Workaround prior to upgrade:
Use configupload/download to
change the TI zone, or modify the
member and the property (failover
disable/enable) together.
User may need to change TI zone member in order to modify TI Zone
property (failover setting).
Fixed in Fabric OS 6.2.0.
SW_RSCNs for RSCNs generated by attached nodes are not being
handled in McDATA Mode.
Fixed in Fabric OS 6.2.0.Legacy zone commands can be used to modify TI zones.
HP StorageWorks Fabric OS 6.2.0g release notes 37