Chapter 7 Troubleshooting Shenzhen Hpmont Technology Co., Ltd
124 HD30 Series Inverters User Manual
Fault code Fault name Possible reasons of fault Counter-measures
E0007 Stall overvoltage
Bus voltage is too high
The setting of stall overvoltage
is too low.
Please check power input or the
function of brake
Set the value of stall
overvoltage properly
E0008
Fault of power
module
Short circuit between phases
output
Short circuit to the ground
Output current is too high
Power module is damaged
Please check the connection and
connect the wire properly
Please check the connection and
connect the wire properly
Please check the connection and
mechanism
Please contact the supplier for
repairing
E0009
Heatsink
overheat
Ambient temperature is too
high
Inverter external ventilation is
not good
Fan fault
Fault occurs to temperature
detection circuit
Please use inverter with higher
power capacity
Improve the ventilation around
the inverter
Replace the cooling fan
Please seek technical support
E0010
Fault of braking
unit
Circuit fault of braking unit Please seek technical support
E0011 CPU fault CPU abnormal
Please detect at power on after
completely power outage
Please seek technical support
E0012
Parameters
auto-tuning fault
Parameter auto-tuning is time
out
Please check the motor’s
connection
Input the correct motor
parameters (F08.00F08.04
F13.01F13.05)
Please seek technical support
E0013
Contactor is not
actuated
Contactor fault
Fault of control circuit
Replace the contactor
Please seek technical support
E0014
Fault of current
detection circuit
Current detection circuit is
damaged
Please contact the supplier for
repairing
E0015
Fault of input
phase
For three-phase input inverter,
input phase loss fault occurs to
power input
Please check the three-phase
power input
Please seek technical support
E0016
Fault of output
phase
Output phase disconnection or
loss
Heavy imbalance of inverter’s
three-phase load
Please check the connection
between inverter and motor
Please check the quality of motor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the hpmont HD30-4T011G/015P and is the answer not in the manual?

hpmont HD30-4T011G/015P Specifications

General IconGeneral
Brandhpmont
ModelHD30-4T011G/015P
CategoryInverter
LanguageEnglish

Related product manuals