Chapter 6 Function Introduction Shenzhen Hpmont Technology Co., Ltd
―62― HD30 Series Inverters User Manual
No. Name Description Range
factory setting
F00.19 Dead time of direction switch 0.0
3600.0
0.0s
F00.19 defines the dead time of direction switch, namely,
the time of zero-frequency output in the process of
direction switch shown as the right figure.
Key enable of optional display panel
0: Enabled. When the inverter connects to two display panels, the keys of optional display using the
communication port can be operated.
1: Invalid. When the inverter connects to two display panels, the keys of optional display using the
communication port can not be operated.
Dormant function selection
0: Disabled. This function is invalid.
1: Enabled. At the running state, when the preset frequency ≤lower limit of operation frequency
(F00.09), the inverter coasts to stop and go into dormant state.
F00.22 Dormancy wake up time 0.0
360.0
0.0s
When the inverter is at the dormancy state, and the preset frequency >lower limit of operation
frequency (F00.09), and the duration achieves the time of F00.22 setting, then the inverter wakes up
from dormancy state, and start at the mode of F02.00 setting.
Forward
Reverse
F00.19
Time
Frequency
0