55
LP-542 REV. 6.2.16
4:OH
68F
Maximum Outdoor Temperature
When used with an outdoor sensor, sets the maximum outdoor design
temperature for the system design. Maximum outdoor temperature must be set
9
o
F above the minimum outdoor temperature.
Range: (Minimum Outdoor Temperature + 9
o
F) to 110
o
F
5:OL
5F
Minimum Outdoor Temperature
Sets the minimum outdoor design temperature for the system. Minimum
outdoor temperature must be set 9
o
F below the maximum outdoor temperature.
Range: -4
o
F to (Maximum Outdoor Temperature - 9
o
F)
6:cH
180F
Maximum Supply Temperature
Sets the maximum design supply temperature based on the minimum outdoor
design temperature. Maximum supply temperature must be set at least 9
o
F
above the minimum supply temperature.
Range: (Minimum Supply Temperature + 9
o
F) - 180
o
F
7:cL
86F
Minimum Supply Temperature
Sets the design supply water temperature based on the maximum outdoor
design temperature. Minimum supply temperature must be set at least 9
o
F
below the maximum supply temperature.
Range: 40
o
F to (Maximum Supply Temperature - 9
o
F) Default: 86
o
F
8:OF
68F
Warm Weather Shutdown
When outdoor temperature sensor is used, warm weather shut down will shut
down CH Mode if the programmed outdoor temperature is exceeded.
Range: 50 - 110
o
F
9:bt
0
Boost Function
When Outdoor Temperature Mode is used, Boost Function increases the CH
set point temperature by the Boost Degree temperature [10:bd]) at time
intervals (Boost Interval [11:bI]). A space heating demand must be active
without a DHW demand over the Boost Function set period of time (9:bt) for
boost to activate. Boost continues until the boiler reaches the maximum supply
temperature set point (6:cH) based on the outdoor reset curve. The boiler will
return to normal operation after the thermostat is satisfied.
Range: 0 - 120 min
NOTE: “0” means boost function is OFF.
10:bd
10F
Boost Degree
Sets the temperature added to the boiler target set point based on the Outdoor
Temperature reset curve.
Range: 5 - 15F Default: 10F
11:bl
20 MIN
Boost Interval
Sets the interval time when the boiler will increase the temperature by the Boost
Degree. Ex: Initial Boost: 10F. After 20 MIN Interval: Boost will increase CH set
point temperature another 10F. After another 20 MIN Interval: Boost will
increase CH set point temperature another 10F. This will continue until the
boiler reaches the maximum supply temperature set point (6:cH) based on the
outdoor reset curve, or until the thermostat is satisfied.
Range: 0 - 120 MIN Default: 20 MIN
12:FH
00
Maximum Fan Speed
Adjusts Maximum Fan Speed
Range: -30 to +30
13:FL
00
Minimum Fan Speed
Adjusts Minimum Fan Speed
Range: -30 to +30
14:dr
NO
Reset burner operation time
Select YES to Initialize burner operation time
Range: NO or YES
15:dI
NO
Reset ignition cycle
Select YES to Initialize ignition cycles
Range: NO or YES
16:Ft
1
CH Anti-Cycling time
This function delays burner operation during CH mode
Range: 0 - 20 min
17:bo
30F
Set differential temperature to turn
burner “ON
When set, the appliance will operate to heat CH water when water temperature
falls below a differential setting.
Example: If set point is 180
o
F and differential is 30
o
F, the appliance will turn on
when CH water temperature falls below 150
o
F.
Range: 5 - 30
o
F
18:cb
100
Heating capacity
Set Heating combustion rate Range: 50 - 100%
19:db
100
DHW capacity
Set DHW combustion rate
Range: 50 - 100%
20:PE
1MIN
Heating Pump Post-Purge Time,
T/T Satisfied
Allows the user to set the appliance pump post purge time once the thermostat
is satisfied. Range: 0-5 minutes
21:dH
120F
Indirect Storage Tank
Temperature Set Point
Sets Maximum Indirect storage tank Temperature
Range:95 - 180
o
F
22:dd
7 F
Indirect Storage Tank Differential
Set Point
DHW Differential Set Point
Range: 5-30 F
23:Pr
1 MIN
DHW Pump Post Run Time
DHW Pump Post Run Time
Range: 0-10 Min
24:DP
30 Min
DHW Priority Timer
DHW Priority Timer
Range: 0 60 Min
NOTE: If zero is selected DHW will always be priority.
25:ST
180F
Boiler Supply Indirect Storage
Tank Temperature
Boiler Supply Indirect Tank Temperature
Range: 120 180 F