Default Value Setting Threshold Factory Setting Remarks
SET Set Point / -55 - 99 °C 25°C
Hy Differential 2.0°C 0.1 - 25 °C 20°C
AC Anti-short cycle delay 1 0 - 50 min 1
Cy Compressor ON time faulty probe 15 0 - 99 min 0
Cn Compressor OFF time faulty probe 30 0 - 99 min 0
CH
Kind of action (Cooling cL, Heating
Ht)
cL cL - Ht Ht
Default Value Setting Threshold Factory Setting Remarks
SET Set Point / -55 - 99 °C 25°C
Hy Differential 2.0°C 0.1 - 25 °C 10°C
AC Anti-short cycle delay 1 0 - 50 min 1
Cy Compressor ON time faulty probe 15 0 - 99 min 0
Cn Compressor OFF time faulty probe 30 0 - 99 min 0
CH
Kind of action (Cooling cL, Heating
Ht)
cL cL - Ht Ht