44
Statement
7
9
FAQ
How Do I Level the ESS When Doors Cannot Be Opened or Closed
1. Use a jack to support the ESS.
•
Jack specification: 30 t
• Position requirements: on the control unit cabin side or its opposite side (the short side of
the ESS container)
2. Adjust the height using leveling washers from the control unit cabin.
Scenario 1: The Upper Part of the Lock Tongue Interferes
With the Upper Surface of the Lock Base
Wood sleepers can be used in the following circumstances.
•
Insufficient jack height: Place wood sleepers underneath the jack.
•
Natural ground surface: Use wood sleepers to extend contact area.
Use leveling washers to raise ESS by 5–10 mm on the foundation under the door hinge.
The raising height leveling washers may vary according to the actual conditions.
This procedure applies only to some models.