Huawei NetCol500-A080 - Oil Trap and Inverted Trap (Unit: mm); Installing the Indoor Unit

Huawei NetCol500-A080
47 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
7/8 inch gas pipe
inverted trap
3/4 inch liquid
pipe inverted trap
5/8 inch liquid
pipe inverted trap
1 inch gas pipe
inverted trap
Oil Trap and Inverted Trap (Unit: mm)
2.2
3
Installing the Indoor Unit
1. Read the related user manual or instructions before installing the NetCol8000-A.
2. The unit in this document is a fully configured NetCol8000-A. If some components are not
configured, skip the corresponding steps.
3. You are recommended to use tools that are fully insulated when installing devices.
4. Only engineers from the manufacturer or engineers certified by the agent are allowed to
install, commission, and maintain the smart cooling product. Otherwise, personal injuries
and device damage may be caused, which is beyond the warranty range.
NetCol8000-A045 Upflow
NetCol8000-A045/A055/090 Downflow
Liquid pipe
needle valve
Exhaust pipe needle valve
Low-pressure needle
valve
Liquid pipe
needle valve
Exhaust pipe
needle valve
Low-pressure
needle valve
Checking Whether the Nitrogen Is Discharged at the Needle Valves
of the Outdoor Unit
3.1
7/8 inch oil trap 1 inch oil trap

Related product manuals