48
2 Selecting Power Cables
Input
Current (A)
Power Cable
Length (m)
Cross-Sectional
Area of the
Power Cable
(mm²)
Terminal Type
63
20 16
DPD63-8-8 PDU NEG(-) and RTN(+) cables:
A cord end terminal must be equipped at the cable end for connecting to
the PDU.
TN16PDU/TN51PDU NEG(-) and RTN(+) cables:
When the cross-sectional area of the NEG(-)/RTN(+) cable is 16 mm² or
25 mm², a two-hole OT terminal must be equipped at the cable end for
connecting to the PDU. When the cross-sectional area is 35 mm², a one-
hole OT terminal must be equipped at the cable end for connecting to the
PDU.
21~35 25
36~50 35
32
20 16
36~50 25
51~80 35
100/125 25 35
DPD63-8-8 PDU NEG(-) and RTN(+) cables:
A two-hole OT terminal must be equipped at the NEG(-) cable end for
connecting to the PDU, and a cord end terminal must be equipped at the
RTN(+) cable end for connecting to the PDU.
TN16PDU/TN51PDU NEG(-) and RTN(+) cables:
A one-hole OT terminal must be equipped at the cable end for connecting
to the PDU.
Determine the required power cables for connecting the PDF to the PDU against the following table. If the length and
cross-sectional area of the power cable do not conform to the specifications listed in the following table, consult with the
product manager at your local representative office.