38 1140 Array Black Start Failed
Alarm Attribute
Alarm ID Alarm Name Alarm Severity
1140 Array Black Start Failed Minor
Possible Cause
Cause ID
Possible Cause
1 The black start command is not
delivered in the correct time sequence.
2 The array running status does not
meet the condition for a black start.
3 No available ESS.
4 The ESS does not support black start.
5 The PCS does not support black start.
6 The black start of the ESS failed.
7 No available PCS.
8 The black start of the PCS failed.
Suggestion
Cause ID=1:
The black start instruction sequence is not supported. Contact the microgrid
controller vendor to correct the sequence.
Cause ID=2:
SmartLogger3000
Alarm Reference 38 1140 Array Black Start Failed
Issue 01 (2023-09-15) Copyright © Huawei Technologies Co., Ltd. 40