2 1100 Active Power Scheduling
Instruction Exception
Alarm Attribute
Alarm ID Alarm Name Alarm Severity
1100 Active Power Scheduling
Instruction Exception
Major
Possible Cause
Cause ID
Possible Cause
4 In DI active scheduling mode for active
power control, instruction
combinations not congured are read
from the four DI ports.
5 In the remote active power scheduling
mode, the SmartLogger cannot receive
the active power scheduling command,
or the received active power
scheduling command is abnormal.
Suggestion
Cause ID=4:
1. Check that cables are connected correctly to the DI ports.
2. Enter the conguration page of the DI active scheduling mode for active
power control, and view the current DI signal conguration mapping table.
Contact the power grid company and verify that the combination
congurations in the table are complete and meet the requirements of the
company.
SmartLogger3000
Alarm Reference
2 1100 Active Power Scheduling Instruction
Exception