Huawei SmartLogger 3000 - 1101 Reactive Power Scheduling Instruction Exception

Huawei SmartLogger 3000
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 1101 Reactive Power Scheduling
Instruction Exception
Alarm Attribute
Alarm ID Alarm Name Alarm Severity
1101 Reactive Power
Scheduling Instruction
Exception
Major
Possible Cause
Cause ID
Possible Cause
4 In DI reactive scheduling mode for
reactive power control, instruction
combinations not congured are read
from the four DI ports.
5 In the remote reactive power
scheduling mode, the SmartLogger
cannot receive the reactive power
scheduling command, or the received
reactive power scheduling command is
abnormal.
Suggestion
Cause ID=4:
1. Check that cables are connected correctly to the DI ports.
2. Enter the conguration page of the DI reactive scheduling mode for reactive
power control, and view the current DI signal conguration mapping table.
Contact the power grid company and verify that the combination
SmartLogger3000
Alarm Reference
3 1101 Reactive Power Scheduling Instruction
Exception
Issue 01 (2023-09-15) Copyright © Huawei Technologies Co., Ltd. 4