3 1101 Reactive Power Scheduling
Instruction Exception
Alarm Attribute
Alarm ID Alarm Name Alarm Severity
1101 Reactive Power
Scheduling Instruction
Exception
Major
Possible Cause
Cause ID
Possible Cause
4 In DI reactive scheduling mode for
reactive power control, instruction
combinations not congured are read
from the four DI ports.
5 In the remote reactive power
scheduling mode, the SmartLogger
cannot receive the reactive power
scheduling command, or the received
reactive power scheduling command is
abnormal.
Suggestion
Cause ID=4:
1. Check that cables are connected correctly to the DI ports.
2. Enter the conguration page of the DI reactive scheduling mode for reactive
power control, and view the current DI signal conguration mapping table.
Contact the power grid company and verify that the combination
SmartLogger3000
Alarm Reference
3 1101 Reactive Power Scheduling Instruction
Exception