Note a: The maximum active power is determined by PQ mode, which can be set on the
SUN2000 app, SmartLogger, or NetEco. If PQ mode 1 is selected, the maximum active
power equals the maximum apparent power. If PQ mode 2 is selected, the maximum active
power equals the rated active power.
Note b: The rated output voltage depends on Grid code, which can be set on the SUN2000
app, SmartLogger, or NMS.
Note c: Choose whether to connect the neutral wire to the SUN2000-29.9KTL,
SUN2000-33KTL-A and SUN2000-36KTL based on the application scenario. When they
are used in the scenarios without the neutral wire, set Output mode to Three-phase,
three-wire. When they are used in the scenarios with the neutral wire, set Output mode to
Three-phase, four-wire.
When the Grid code for the SUN2000-36KTL is set to Mexico-MV480, and the
SUN2000-36KTL is used for power generation in 440 V AC grid connection, you need to
adjust the level-1 and level-2 undervoltage protection threshold to 384 V. The proper AC
output voltage is within the range of 384–576 V.