Ambient temperature: 0–40ºC
Humidity: 0–95% RH (non-condensing)
• Input voltage for standard version: 220 
V AC, 230 V AC, or 240 V AC (single-
phase input); Input voltage for 
professional version: 208 V AC, 220 V 
AC, 230 V AC, or 240 V AC (single-
phase input).
Output voltage for standard version: 
220 V AC, 230 V AC, or 240 V AC 
(single-phase output); Output voltage 
for professional version: 208 V AC, 220 
V AC, 230 V AC, or 240 V AC (single-
phase output). 
If the humidity and temperature 
are abnormal, check the air 
conditioner status.
If the input voltage is abnormal, 
check the power grid status and 
input cable connection.
• If the output voltage is abnormal, 
check the UPS running status 
and check whether an alarm is 
present.
Check that all units are operating properly 
by observing the status icons on the LCD, 
all operating parameters are within their 
normal ranges, and no fault or alarm 
information is displayed.
If an alarm is present, rectify the 
fault by checking the device status 
and parameters.
No abnormal noise is generated.
Check where the abnormal noise 
comes from, especially fans, input 
and output transformer (if 
configured). If the problem is not 
resolved, contact 
Wipe the cabinet surface using a white 
paper and the paper does not turn black.
See related parameter setting descriptions 
in 
UPS2000-A-(6 kVA-10 kVA) User 
Cables are intact and do not deteriorate 
or damage.
If a cable is damaged, find the 
reason and apply protective 
measures such as rodent
Regularly check and record the 
adding and removal of loads.
Categorize exceptions and alarms.
Analyze and export alarm analysis 
report.
Routine Maintenance
1
UPS Monthly Maintenance
This section describes the monthly maintenance for the UPS and batteries. For more detailed 
maintenance information, see the 
UPS2000-A-(6 kVA-10 kVA) User Manual
.