16
Item Expected Result Measures
Charge 
current
≤ 2 A (standard model)
≤ 8 A (long backup time 
model)
If the charge current is incorrect, contact Huawei
technical support.
Battery string 
charge 
voltage
Equalized voltage 14.1 V x 
Number of batteries 
(tolerance ±1%)
Float voltage 13.5 V x 
Number of batteries 
(tolerance ±1%)
1. If the voltage drop between the battery 
string output terminals and the battery input 
terminals at the UPS host side is greater than 
1% of the battery string voltage, check 
whether the cable between the battery string 
and the UPS is excessively long, or the cable 
diameter is excessively small.
2. Check whether the equalized charging 
voltage and float charging voltage are 
correctly set for the UPS host.
3. If the fault persists, contact Huawei technical 
support.
Battery 
appearance
1.
The battery shell is intact, 
without acid leaks, 
deformation, or bulges.
2. The battery is free from 
dust or dirt.
1. Take photos of any deformed or faulty parts 
of batteries.
2. Check and record the charge voltage and 
current of the battery string as well as the 
voltage of each battery.
3. Check the battery surface temperature.
4. Keep deformed and bulged faulty batteries 
still for 30 minutes and then check and 
record open-circuit voltage of the faulty 
battery.
5. If the fault persists, contact Huawei technical 
support.
Battery 
management 
parameters
Parameters settings of 
battery number, battery 
capacity, battery charge 
voltage, battery charge 
current, and EOD setting 
values meet requirements. 
The capacity value matches 
the actual value.
Set parameters correctly.
Battery alarm No battery alarm is 
generated.
Identify the cause based on the alarm 
information.
Battery 
connection
Battery terminals and cables 
are in good contact.
Ensure that battery terminals and cables are in 
good contact.
Battery 
operating 
temperature
1. The difference between 
temperature reported by 
the battery temperature 
sensor and the actual 
temperature is less than 
2ºC.
2. The service temperature 
of a working battery does 
not exceed 45ºC.
1. Identify the cause of the false temperature 
sensor alarm.
2. Identify the cause of the abnormal battery 
operating temperature.
3. If the fault persists, contact Huawei technical 
support.
2