Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0060-04 Inverter
fault
Critical Power-
o
The UPS shuts down
immediately, supplies no
power, and protects loads.
Possible cause: The
inverter output is short-
circuited.
Measure: Rectify output
port short circuits. After
you clear the alarm,
restart the UPS. If the
alarm persists, contact
Huawei technical
support for repair.
0060-05 Inverter
fault
Critical Automa
tic
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
Possible causes:
The mains
experiences
instantaneous high-
voltage impact.
The output has
special loads such as
sensitive loads and
rectication loads.
The output has
transformer loads
but the transformer
mode is not set.
The hardware is
faulty.
Measures:
After you rectify the
fault, restart the UPS.
Check whether the
load type is
supported by the
UPS.
Enable the
transformer mode.
Contact Huawei
technical support for
repair.