Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0060-07 Inverter
fault
Critical Automa
tic
The UPS starts automatically
after shutdown.
The UPS may transfer to
another working mode or
shut down.
Possible causes:
The ambient
temperature exceeds
40ºC.
The air channel is
blocked.
The air
lter is
blocked by dust.
The fan is abnormal.
Measures:
Decrease the
ambient
temperature.
Keep the air intake
and exhaust vents of
the UPS
unobstructed.
Clean or replace the
air
lter.
Clean o the foreign
objects around the
fan. If the alarm
persists, contact
Huawei technical
support for repair.
0060-08
Inverter
fault
Critical Manual
/Power-
o
The UPS shuts down. Possible cause: The DSP
or CPLD chip is faulty.
Measure: Contact
Huawei technical
support for repair.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 163