The main power is 
normal, but no indicator 
turns on and the buzzer 
generates no tone.
The mains input power cable is 
disconnected.
Check the input power cable.
The mains input power cable is 
incorrectly connected to the UPS 
output end.
Correctly connect the mains input 
power cable to the UPS input 
terminal.
LCD and the buzzer 
beeps once every 
second.
The external or internal batteries 
are incorrectly connected.
Check that all batteries are 
connected correctly.
LCD and the buzzer 
beeps twice every 
second.
Remove surplus load from the UPS 
output end.
The UPS is overloaded and 
supplying power to devices in 
bypass mode.
Remove surplus load from the UPS 
output end.
The UPS is overloaded server times 
within a short period of time. The 
UPS is locked in bypass mode and 
loads are directly connected to the 
main power source.
Remove surplus load from the UPS 
output end, and then shut down 
and restart the UPS.
The battery backup time 
is shorter than the time 
given in specifications.
Batteries are not fully charged.
Charge batteries for at least 5 
hours and then check the battery 
capacity. If the battery capacity is 
still insufficient, contact the dealer.
Contact the dealer to replace 
batteries.