UPS2000-G-(1 kVA-3 kVA) 
User Manual 
 
Copyright © Huawei Technologies Co., Ltd. 
 
and no fault or alarm 
information is 
displayed in active 
alarm or historical 
alarms. 
Wipe the cabinet 
surface using a white 
paper and the paper 
does not turn black. 
Clean the dust, 
especially in the 
front panel. 
Check the output 
voltage level and 
frequency, the 
number of batteries 
and the actual battery 
capacity. 
Power cables and 
terminals (between 
the UPS and external 
power distribution 
equipment) 
The insulation layers 
of cables are intact 
and terminals are 
free from noticeable 
sparks. 
 
Replace the 
cables. 
 
Secure the output 
terminals. 
No battery alarm is 
generated. 
If an alarm is 
present, rectify the 
fault. 
 
7.2 Battery Maintenance 
 
 
Before installing batteries, read through the battery user manuals and pay attention to safety 
precautions and connection methods provided by battery manufacture. 
When installing and maintaining batteries, pay attention to the following points: 
 
Wrap tools with insulation tape to prevent electric shock. 
 
Protect your eyes with relevant devices and apply other protective measures. 
 
Wear rubber gloves and a protective coat in case of electrolyte overflow. 
 
When moving batteries, avoid handling the battery upside down, handle batteries gently, 
and pay attention to personal safety. 
 
Keep the battery switch off when installing or maintaining the batteries.