The configured number of batteries must match the actual number. When the actual number 
changes, change the configured number. If the configured number is less than the actual 
number, the battery lifespan is shortened. If the configured number is greater than the actual 
number, battery leakage may cause a fire. 
 
 
 
If the system uses three-phase input three-phase output, set Output mode to Three-phase. 
If the system uses three-phase input single-phase output or single-phase input single-phase 
output, set Output mode to Single-phase. 
 
Set Voltage level and Frequency level based on the rated voltage and frequency. In the 
case of single-phase output, set Voltage level to 220 V (default), 230 V, or 240 V; in the 
case of three-phase output, set Voltage level to 380 V (default), 400 V, or 415 V.   
 
Battery parameters are configurable in non-battery mode or non-battery ECO mode. 
 
Set Positive batteries and Negative batteries. The value ranges from 16 to 20. The 
default value is 20. 
 
Set Battery capacity to the total capacity of all batteries actually connected. The value 
ranges from 7 Ah to 1000 Ah. The default value is 65 Ah. 
This section describes how to start the UPS2000-G-15 kVA/20 kVA. 
Figure 5-1 Connecting cables to the UPS2000-G-15 kVA/20 kVA (three-phase input three-phase 
output, dual mains) 
 
 
Starting the UPS in Normal Mode 
Step 1  Close the external battery circuit breaker (if there is), or connect battery cables. 
Step 2  Close the UPS mains input circuit breaker K
m
1 and bypass input circuit breaker K
b
1.