Loading...
UPS2000-G-(6 kVA-20 kVA)
User Manual
9 Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
90
Item
6 kVA
10 kVA
15 kVA
20 kVA
Double-pow
er input
Disabled
Disabled
Enabled
Enabled
Startup
voltage
120280 V AC
Diesel
generator
input
capacity
Minimum 1.5 times the UPS rated capacity
9.4 Bypass Input Electrical Specifications
Table 9-4 Bypass input electrical specifications
Item
6 kVA
10 kVA
15 kVA
20 kVA
Bypass voltage
Upper threshold: 10%/15%/20%/25%@220 V AC
Upper threshold: 10%/15%/20%@230 V AC
Upper threshold: 10%/15%@240 V AC
Lower threshold: 10%/20%/30%/40%/50%/60%
Bypass frequency
tolerance
Maximum ±6 Hz (configurable on the LCD)
Bypass overload
capability
Load < 125%: continuous in bypass mode
125% ≤ load < 150%: 1 minute in bypass mode
Load ≥ 150%: 100 milliseconds in bypass mode
The input switch may trip in advance.
Input mode
One mains input
One mains input
Two mains inputs
The upper and lower thresholds are configurable on the LCD.
9.5 Output Electrical Specifications
Table 9-5 Output electrical specifications
Item
6 kVA
10 kVA
15 kVA
20 kVA