Perform "startup operations": On the standby screen, hold down       for about 5 seconds. Release 
the button when you hear a beep tone. The startup screen is displayed. If the UPS starts 
successfully, it enters the normal mode. After you ensure that the UPS runs properly, turn on the 
AC output circuit breaker (Q1) to start loads.
Perform "shutdown operations" to shut down the UPS: On the default screen, hold down ESC for 
more than 5 seconds. Release the button when you hear a beep tone. The inverters shut down. If 
the bypass voltage is within the configured range, the UPS transfers to bypass mode. If the 
bypass voltage is beyond the configured range, the UPS has no output. 
8
Shutting Down the UPS
1. Shut down loads.
2. Perform "shutdown operations" on the UPS. The inverters shut down. If the bypass voltage is 
within the configured range, the UPS transfers to bypass mode. If the bypass voltage is beyond 
the configured range, the UPS has no output.
3. Turn off the UPS AC input circuit breaker (K1) and output circuit breaker (Q1).
4. Turn off the external battery circuit breakers (if there are), or disconnect battery power cables 
(if there is no battery circuit breaker). After all indicators turn off and fans stop, the UPS shuts 
down and stops supplying power to loads.
1
2
Shutting Down Inverters to Transfer the UPS to Bypass Mode
8.1
Powering Off the UPS
8.2
More 
than 5 
seconds